Minimum Energy Compensation Strategy and Characteristic Analysis for Dynamic Voltage Restorer

被引:0
作者
Liu, Yingying [1 ]
Xu, Yonghai [1 ]
Xiao, Xiangning [1 ]
Guo, Chunlin [1 ]
机构
[1] N China Elect Power Univ, Sch Elect & Elect Engn, Beijing 102206, Peoples R China
来源
ICEET: 2009 INTERNATIONAL CONFERENCE ON ENERGY AND ENVIRONMENT TECHNOLOGY, VOL 2, PROCEEDINGS | 2009年
关键词
dynamic voltage restorer; minimum energy compensation; compensation strategy; compensation characteristic; voltage limitation;
D O I
10.1109/ICEET.2009.279
中图分类号
TE [石油、天然气工业]; TK [能源与动力工程];
学科分类号
0807 ; 0820 ;
摘要
the minimum energy compensation strategy and its characteristic for Dynamic Voltage Restorer (DVR) considering the equipment's voltage limitation are discussed. The strategy when the injection voltage is under or especially above the voltage limitation is proposed. And the detailed expressions of the strategy which show that the compensation effect is influenced by three factors magnitude of the system voltage sag (or swell), power factor of load and limitation value of the compensation voltage were given. The compensation characteristic that DVR could operate in zero, minimum or voltage limitation minimum active power exchange state if the three factors satisfy certain relations was analyzed. Last, the quantitative curves of the compensation characteristic were given. The analysis results will be helpful to compensation strategy design and engineering practice for DVR.
引用
收藏
页码:172 / 175
页数:4
相关论文
共 11 条
[1]   A generalized voltage compensation strategy for mitigating the impacts of voltage sags/swells [J].
Choi, SS ;
Li, JD ;
Vilathgamuwa, DM .
IEEE TRANSACTIONS ON POWER DELIVERY, 2005, 20 (03) :2289-2297
[2]  
Feng Xiaoming, 2004, Automation of Electric Power Systems, V28, P68
[3]  
Huang Xin-ming, 2007, Proceedings of the CSEE, V27, P120
[4]  
Lam C. S., 2005, Automation of Electric Power Systems, V29, P35
[5]   Control strategy for dynamic voltage restorers to achieve minimum power injection without introducing sudden phase shift [J].
Li, G. J. ;
Zhang, X. P. ;
Choi, S. S. ;
Lie, T. T. ;
Sun, Y. Z. .
IET GENERATION TRANSMISSION & DISTRIBUTION, 2007, 1 (05) :847-853
[6]   Optimized control strategy for a medium-voltage DVR [J].
Meyer, C ;
Romaus, C ;
De Doncker, RW .
2005 IEEE 36TH POWER ELECTRONIC SPECIALISTS CONFERENCE (PESC), VOLS 1-3, 2005, :1887-1893
[7]   An energy-saving series compensation strategy subject to injected voltage and input-power limits [J].
Wang, Q. ;
Choi, S. S. .
IEEE TRANSACTIONS ON POWER DELIVERY, 2008, 23 (02) :1121-1131
[8]  
Xiao Guo-chun, 2008, Proceedings of the CSEE, V28, P114
[9]  
Xu Xie, 2002, AUTOMATION ELECT POW, P41
[10]  
Yuan Chuan, 2004, Automation of Electric Power Systems, V28, P49