Decision tree-induced fuzzy rule-based differential relaying for transmission line including unified power flow controller and wind-farms

被引:43
作者
Jena, Manas Kumar [1 ]
Samantaray, Subhransu Ranjan [1 ]
Tripathy, Lokanath [1 ]
机构
[1] Indian Inst Technol Bhubaneswar, Sch Elect Sci, Bhubaneswar, Orissa, India
关键词
FAULT CLASSIFICATION; IDENTIFICATION; INDUCTION;
D O I
10.1049/iet-gtd.2014.0023
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
The paper presents a decision tree (DT) induced fuzzy rule-based intelligent differential relaying scheme for transmission lines including unified power flow controller (UPFC) and wind-farms. The conventional distance relaying scheme fails miserably in protecting transmission lines including flexible AC transmission systems controllers such as UPFC and further, the protection issues become more challenging when wind-farm is integrated. The proposed protection scheme extracts features from the instantaneous voltage and current signals from both ends of the transmission line using discrete Fourier transform based pre-processor and computes corresponding differential features. The differential features are used to build the fault classification tree using a data-mining algorithm known as DT. Further, the fuzzy membership functions are drawn using the DT thresholds and the corresponding fuzzy rule-base is developed for final relaying decision. The proposed technique has been extensively tested (in MATLAB environment) for single circuit and double circuit transmission lines including UPFC and wind-farms with wide variations in operating conditions. The test results indicate that the proposed DT-induced fuzzy rule-based relaying scheme is highly reliable and robust for protection of complex transmission line including UPFC and wind-farm.
引用
收藏
页码:2144 / 2152
页数:9
相关论文
共 26 条
[1]  
[Anonymous], 2008, RATTLE R ANAL TOOL L
[2]  
[Anonymous], 1984, OLSHEN STONE CLASSIF, DOI 10.2307/2530946
[3]   A comparison of decision tree ensemble creation techniques [J].
Banfield, Robert E. ;
Hall, Lawrence O. ;
Bowyer, Kevin W. ;
Kegelmeyer, W. P. .
IEEE TRANSACTIONS ON PATTERN ANALYSIS AND MACHINE INTELLIGENCE, 2007, 29 (01) :173-180
[4]   On constructing a fuzzy inference framework using crisp decision trees [J].
Crockett, Keeley ;
Bandar, Zuhair ;
Mclean, David ;
O'Shea, James .
FUZZY SETS AND SYSTEMS, 2006, 157 (21) :2809-2832
[5]   Adaptive Current Differential Protection Schemes for Transmission-Line Protection [J].
Dambhare, Sanjay ;
Soman, S. A. ;
Chandorkar, M. C. .
IEEE TRANSACTIONS ON POWER DELIVERY, 2009, 24 (04) :1832-1841
[6]   Fault classification and section identification of an advanced series-compensated transmission line using support vector machine [J].
Dash, P. K. ;
Samantaray, S. R. ;
Panda, Ganapati .
IEEE TRANSACTIONS ON POWER DELIVERY, 2007, 22 (01) :67-73
[7]   Dynamic modeling of doubly fed induction generator wind turbines [J].
Ekanayake, JB ;
Holdsworth, L ;
Wu, XG ;
Jenkins, N .
IEEE TRANSACTIONS ON POWER SYSTEMS, 2003, 18 (02) :803-809
[8]  
Hingorani N. G., 2000, Understanding FACTS Concepts and Technology of Flexible AC Transmission Systems
[9]   A Decision-Tree-Based Method for Fault Classification in Single-Circuit Transmission Lines [J].
Jamehbozorg, Arash ;
Shahrtash, S. Mohammad .
IEEE TRANSACTIONS ON POWER DELIVERY, 2010, 25 (04) :2190-2196
[10]   An adaptive relaying for the protection of a wind farm interconnected with distribution networks [J].
Jang, SI ;
Choi, JH ;
Kim, JW ;
Choi, DM ;
Kim, KH .
2003 IEEE PES TRANSMISSION AND DISTRIBUTION CONFERENCE & EXPOSITION, VOLS 1-3, CONFERENCE PROCEEDINGS: BLAZING TRAILS IN ENERGY DELIVERY AND SERVICES, 2003, :296-302