Online Tracking of Transmission-Line Parameters Using SCADA Data

被引:51
作者
Wang, Yang [1 ]
Xu, Wilsun [1 ]
Shen, James [2 ]
机构
[1] Univ Alberta, Dept Elect & Comp Engn, Edmonton, AB T6G 2R3, Canada
[2] Alberta Elect Syst Operator, Calgary, AB T2P 0L4, Canada
基金
加拿大自然科学与工程研究理事会;
关键词
Energy-management system (EMS); line parameters; phasor measurement unit (PMU); supervisory control and data acquisition (SCADA);
D O I
10.1109/TPWRD.2015.2474699
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
Series impedance and shunt admittance parameters of transmission lines are fundamental data for various online and offline power system studies. This paper shows that the active power, reactive power, and voltage magnitude (P, Q, V) data measured at the two ends of a transmission line are sufficient to determine the positive-sequence line parameters. The phase-angle information is not essential. Since the P, Q, and V data are readily available from the supervisory control and data-acquisition systems, the proposed method can be easily implemented in existing control centers. Algorithms, characteristics, performances, and potential applications of the proposed method are presented in this paper. Simulation study and field test results show that the proposed technique can be a useful addition to the energy-management systems of utility companies.
引用
收藏
页码:674 / 682
页数:9
相关论文
共 20 条
[1]  
Abur A., 2004, POWER SYSTEM STATE E
[2]  
[Anonymous], 1994, Power System Analysis
[3]  
[Anonymous], 2008, C3712007 IEEE
[4]  
[Anonymous], 2009, 11592009 IEEE
[5]   A Novel Fault-Location Algorithm for Double-Circuit Transmission Lines Without Utilizing Line Parameters [J].
Apostolopoulos, Christos A. ;
Korres, George N. .
IEEE TRANSACTIONS ON POWER DELIVERY, 2011, 26 (03) :1467-1478
[6]   A Novel Algorithm for Locating Faults on Transposed/Untransposed Transmission Lines Without Utilizing Line Parameters [J].
Apostolopoulos, Christos A. ;
Korres, George N. .
IEEE TRANSACTIONS ON POWER DELIVERY, 2010, 25 (04) :2328-2338
[7]  
Bi TS, 2008, 2008 THIRD INTERNATIONAL CONFERENCE ON ELECTRIC UTILITY DEREGULATION AND RESTRUCTURING AND POWER TECHNOLOGIES, VOLS 1-6, P1657
[8]   Robust Calculation of Frequency-Dependent Transmission-Line Transformation Matrices Using the Levenberg-Marquardt Method [J].
Chrysochos, Andreas I. ;
Papadopoulos, Theofilos A. ;
Papagiannis, Grigoris K. .
IEEE TRANSACTIONS ON POWER DELIVERY, 2014, 29 (04) :1621-1629
[9]   On-line estimation of transmission line parameters, temperature and sag using PMU measurements [J].
Du, Yan ;
Liao, Yuan .
ELECTRIC POWER SYSTEMS RESEARCH, 2012, 93 :39-45
[10]  
Glover J. D., 2003, POWER SYSTEM ANAL DE