A Method for Averting Saturation From Series Transformers of Dynamic Voltage Restorers

被引:19
作者
Fernandes, Darlan A. [1 ]
Costa, Fabiano F. [2 ]
Vitorino, Montie A. [3 ]
机构
[1] Fed Univ Paraiba UFPB, Dept Elect Engn, BR-58051900 Joao Pessoa, Paraiba, Brazil
[2] Fed Univ Bahia UFBA, Dept Elect Engn, BR-40210630 Salvador, BA, Brazil
[3] Fed Univ Campina Grande UFCG, Dept Elect Engn, Ctr Elect Engn & Informat, BR-58429900 Campina Grande, PB, Brazil
关键词
Dynamic voltage restorer (DVR); flux linkage; power quality (PQ); recursive least squares; saturation; transformer; CONTROL SCHEME; DVR;
D O I
10.1109/TPWRD.2014.2311577
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
This paper proposes a technique for preventing saturation in series transformers from dynamic voltage restorer (DVR) systems. The method consists in correcting the voltages which are injected through the transformers into the power system to compensate voltage sags. It restricts the compensating voltages during the sag whenever it predicts that a maximum limit for the flux linkage is about to be exceeded. The prediction is carried out at the beginning of a stabilized voltage sag. Moreover, the technique allows a certain level of sag compensation even when the estimated flux is expected to exceed the saturation limit. The voltage sag level and phase are computed through an adaptive recursive least squares (RLS). The RLS estimation incorporates a transient period before it achieves a stable state whenever there is a sag event. The DVR is not supposed to operate in this period. Therefore, this paper also outlines a simple procedure for detecting the RLS estimation stable level. Simulation of different scenarios of voltage sags and the results from the experimental implementation of a DVR show the effectiveness of the method.
引用
收藏
页码:2239 / 2247
页数:9
相关论文
共 21 条
[1]   A new fast-converged estimation approach for Dynamic Voltage Restorer (DVR) to compensate voltage sags in waveform distortion conditions [J].
Abdollahzadeh, Hamed ;
Jazaeri, Mostafa ;
Tavighi, Arash .
INTERNATIONAL JOURNAL OF ELECTRICAL POWER & ENERGY SYSTEMS, 2014, 54 :598-609
[2]   Fault Current Interruption by the Dynamic Voltage Restorer [J].
Ajaei, Firouz Badrkhani ;
Farhangi, Shahrokh ;
Iravani, Reza .
IEEE TRANSACTIONS ON POWER DELIVERY, 2013, 28 (02) :903-910
[3]   A Fast and Effective Control Scheme for the Dynamic Voltage Restorer [J].
Ajaei, Firouz Badrkhani ;
Afsharnia, Saeed ;
Kahrobaeian, Alireza ;
Farhangi, Shahrokh .
IEEE TRANSACTIONS ON POWER DELIVERY, 2011, 26 (04) :2398-2406
[4]  
[Anonymous], 1999, SYSTEM IDENTIFICATIO
[5]   Monitor Placement for Reliable Estimation of Voltage Sags in Power Networks [J].
Avendano-Mora, Manuel ;
Milanovic, Jovica V. .
IEEE TRANSACTIONS ON POWER DELIVERY, 2012, 27 (02) :936-944
[6]   An Inrush Mitigation Technique of Load Transformers for the Series Voltage Sag Compensator [J].
Chen, Yu-Hsing ;
Lin, Chang-Yi ;
Chen, Jhao-Ming ;
Cheng, Po-Tai .
IEEE TRANSACTIONS ON POWER ELECTRONICS, 2010, 25 (08) :2211-2221
[7]   A transformer inrush mitigation method for series voltage sag compensators [J].
Cheng, Po-Tai ;
Chen, Wei-Ting ;
Chen, Yu-Hsing ;
Ni, Chia-Long ;
Lin, Jarsun .
IEEE TRANSACTIONS ON POWER ELECTRONICS, 2007, 22 (05) :1890-1899
[8]  
Costa F. F., 2013, IEEE INT C EL POW EN
[9]   Digital-Scalar PWM Approaches Applied to Four-Leg Voltage-Source Inverters [J].
Fernandes, Darlan Alexandria ;
Costa, Fabiano Fragoso ;
dos Santos, Euzeli Cipriano, Jr. .
IEEE TRANSACTIONS ON INDUSTRIAL ELECTRONICS, 2013, 60 (05) :2022-2030
[10]   Mitigation of saturation in dynamic voltage restorer connection transformers [J].
Fitzer, C ;
Arulampalam, A ;
Barnes, M ;
Zurowski, R .
IEEE TRANSACTIONS ON POWER ELECTRONICS, 2002, 17 (06) :1058-1066