Two case studies on structural analysis of transmission towers under downburst

被引:15
|
作者
Yang, FengLi [1 ]
Zhang, HongJie [1 ]
机构
[1] China Elect Power Res Inst, Dept Engn Mech, Beijing 100055, Peoples R China
基金
中国国家自然科学基金;
关键词
downburst; wind speed profile; transmission tower; wind load; failure mode; TORNADO; MODEL;
D O I
10.12989/was.2016.22.6.685
中图分类号
TU [建筑科学];
学科分类号
0813 ;
摘要
Downbursts are of great harm to transmission lines and many towers can even be destroyed. The downburst wind field model by Chen and Letchford was applied, and the wind loads of two typical transmission towers in inland areas and littoral areas were calculated separately. Spatial finite element models of the transmission towers were established by elastic beam and link elements. The wind loads as well as the dead loads of conductors and insulators were simplified and applied on the suspension points by concentrated form. Structural analysis on two typical transmission towers under normal wind and downburst was completed. The bearing characteristics and the failure modes of the transmission towers under downburst were determined. The failure state of tower members can be judged by the calculated stress ratios. It shows that stress states of the tower members were mainly controlled by 45 degree wind load. For the inland areas with low deign wind velocity, though the structural height is not in the highest wind velocity zone of downburst, the wind load under downburst is much higher than that under normal wind. The main members above the transverse separator of the legs will be firstly destroyed. For the littoral areas with high deign wind velocity, the wind load under downburst is lower than under normal wind. Transmission towers are not controlled by the wind loads from downbursts in design process.
引用
收藏
页码:685 / 701
页数:17
相关论文
共 50 条
  • [21] ANALYSIS AND DESIGN OF GUYED TRANSMISSION TOWERS - CASE-STUDY IN KUWAIT
    ELGHAZALY, HA
    ALKHAIAT, HA
    COMPUTERS & STRUCTURES, 1995, 55 (03) : 413 - 431
  • [22] Behaviour of guyed transmission line structures under downburst wind loading
    Shehata, A. Y.
    El Damatty, A. A.
    WIND AND STRUCTURES, 2007, 10 (03) : 249 - 268
  • [23] Study on Stability of Transmission Tower-Line System under a Downburst
    Zhong, Yongli
    Li, Shun
    Yan, Zhitao
    Liu, Xinpeng
    Luo, Jun
    Jin, Weichen
    BUILDINGS, 2022, 12 (09)
  • [24] FREQUENCY DOMAIN METHOD FOR DYNAMIC RESPONSES OF TRANSMISSION TOWER UNDER DOWNBURST
    Wang, Da-Hai
    Wang, Guo-Qiang
    Wang, Xin
    Sun, Qi-Gang
    Yang, Qing-Shan
    Huang, Guo-Qing
    Yang, Jun-Yong
    Gongcheng Lixue/Engineering Mechanics, 2024, 41 (08): : 152 - 163
  • [25] Damage to transmission towers under thunderstorm winds
    Calotescu, Ileana
    Bîrsan, Marius
    ce/papers, 2021, 4 (2-4) : 283 - 288
  • [26] Dynamic response of transmission line conductors under downburst and synoptic winds
    Aboshosha, Haitham
    El Damatty, Ashraf
    WIND AND STRUCTURES, 2015, 21 (02) : 241 - 272
  • [27] Finite element modeling of transmission line under downburst wind loading
    Shehata, AY
    El Damatty, AA
    Savory, E
    FINITE ELEMENTS IN ANALYSIS AND DESIGN, 2005, 42 (01) : 71 - 89
  • [28] Failure probability analysis of transmission towers under ice-wind interaction
    Li J.
    Wang W.
    Fu X.
    Jiang W.
    Dong Z.
    Zhendong yu Chongji/Journal of Vibration and Shock, 2024, 43 (03): : 136 - 146
  • [29] Nonlinear Pushover Analysis of Retrofitted Transmission Towers Under Static Wind Loads
    Vu, Quang-Viet
    Lee, Hyeok-Ju
    Kim, Jae-Min
    BUILDINGS, 2025, 15 (05)
  • [30] Testing in-phase Analysis for Adjacent Transmission Towers under Ambient Vibration
    Yan, Xiang Mei
    VIBRATION, STRUCTURAL ENGINEERING AND MEASUREMENT I, PTS 1-3, 2012, 105-107 : 112 - 116