DC fault current limiting effect of MMC submodule capacitors

被引:22
作者
Li, Xiaoqian [1 ]
Zhao, Biao [1 ]
Wei, Yingdong [1 ]
Xie, Xiaorong [1 ]
Hu, Yinghong [2 ]
Shu, Dewu [3 ]
机构
[1] Tsinghua Univ, Dept Elect Engn, Beijing 100084, Peoples R China
[2] North China Elect Power Res Inst, Beijing 100045, Peoples R China
[3] Shanghai Jiao Tong Univ, Dept Elect Engn, Shanghai 200240, Peoples R China
基金
中国国家自然科学基金;
关键词
DC fault; Fault current limiting (FCL); Modular multilevel converter (MMC); Submodule (SM) capacitor; MODULAR MULTILEVEL CONVERTER; CIRCUIT-BREAKERS; COORDINATION; PROTECTION; OPERATION; TOPOLOGY;
D O I
10.1016/j.ijepes.2019.105444
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
DC short-circuit fault is a crucial issue in DC grids because the DC fault current increases rapidly with accompanying high fault energy. Limiting the DC fault current is a promising solution to simplify the design of the DC breaker and DC protection. The majority of existing DC fault current limiting (FCL) approaches relies on extra devices, such as DC line inductors. However, the control ability of modular multilevel converters (MMCs) is not optimized. In this study, the submodule (SM) capacitor dynamics during the short DC fault procedure was considered a new control objective, and its effect on the limiting DC fault current was analyzed and revealed. The complex time-varying DC fault transient circuit was comprehensively represented by introducing two base circuit structures and one duty cycle index D. The averaged circuit model was proposed on the basis of the state-space averaging method, which can intuitively show the relation between SM capacitor and DC fault current. The analytical expressions of the DC fault current was given, which can guide the design of the DC FCL control of MMC. The duty cycle index D can represent the discharge of SM capacitors, and the increasing speed of the DC fault current declines with the decrease in D. Accordingly, a feasible FCL control strategy was proposed by choosing D as a tool for affecting and controlling the DC fault current. The proposed FCL control strategy can evidently reduce dc fault current, and avoid the drawbacks of the conventional block or bypass approaches. The simulation results validated the effectiveness of the proposed analysis method and corresponding conclusions.
引用
收藏
页数:9
相关论文
共 31 条
[1]  
[Anonymous], IEEE T POWER DEL
[2]  
[Anonymous], 2012, TECH REP
[3]   A Model-Based Control Scheme for Modular Multilevel Converters [J].
Boernklau, Hans ;
Gensior, Albrecht ;
Rudolph, Joachim .
IEEE TRANSACTIONS ON INDUSTRIAL ELECTRONICS, 2013, 60 (12) :5359-5375
[4]   Research on application of superconducting fault current limiter in MMC- MTDC [J].
Lv, Cheng ;
Tai, Nengling ;
Jin, Zhijian ;
Zheng, Xiaodong .
Journal of Engineering, 2017, 2017 (13) :1307-1311
[5]  
Chuanyue L, 2015, PROC 2015 50 INT U P, P1
[6]   Modular Multilevel Converter DC Fault Protection [J].
Cwikowski, O. ;
Wickramasinghe, H. R. ;
Konstantinou, G. ;
Pou, J. ;
Barnes, M. ;
Shuttleworth, R. .
IEEE TRANSACTIONS ON POWER DELIVERY, 2018, 33 (01) :291-300
[7]   Operating DC Circuit Breakers With MMC [J].
Cwikowski, Oliver ;
Wood, Alan ;
Miller, Allan ;
Barnes, Mike ;
Shuttleworth, Roger .
IEEE TRANSACTIONS ON POWER DELIVERY, 2018, 33 (01) :260-270
[8]   Operation, Control, and Applications of the Modular Multilevel Converter: A Review [J].
Debnath, Suman ;
Qin, Jiangchao ;
Bahrani, Behrooz ;
Saeedifard, Maryam ;
Barbosa, Peter .
IEEE TRANSACTIONS ON POWER ELECTRONICS, 2015, 30 (01) :37-53
[9]   HVDC Circuit Breakers: A Review Identifying Future Research Needs [J].
Franck, Christian M. .
IEEE TRANSACTIONS ON POWER DELIVERY, 2011, 26 (02) :998-1007
[10]   A DC fault handling method of the MMC-based DC system [J].
Li, Bin ;
Li, Ye ;
He, Jiawei .
INTERNATIONAL JOURNAL OF ELECTRICAL POWER & ENERGY SYSTEMS, 2017, 93 :39-50