Development of a new multi-stage building energy model calibration methodology and validation in a public library

被引:59
作者
Cacabelos, Anton [1 ]
Eguia, Pablo [2 ]
Febrero, Lara [2 ]
Granada, Enrique [2 ]
机构
[1] Naval Acad, Def Univ Ctr, Marin 36920, Spain
[2] Univ Vigo, Sch Ind Engn, Lagoas Marcosende S-N, Vigo 36310, Spain
关键词
Multi-stage calibration; Building energy model; TRNSYS; GenOpt; ASHRAE guideline 14; Ground-Source; Heat pump; Radiant floor; SOURCE HEAT-PUMP; SENSITIVITY-ANALYSIS; UNCERTAINTY ANALYSIS; SIMULATION; PERFORMANCE; SYSTEM; CONSUMPTION; EXCHANGERS; EFFICIENCY;
D O I
10.1016/j.enbuild.2017.04.071
中图分类号
TU [建筑科学];
学科分类号
0813 ;
摘要
Calibration of a Building Energy Model (BEM) is necessary to reduce the discrepancies between the simulation results and real data. This research work proposes a novel ground-breaking calibration methodology that divides the entire building into different sub-models and calibrates them separately to obtain an accurate model. To validate this new procedure, a public library Heating, Ventilation and Air Conditioning (HVAC) system with a Ground-Source Heat Pump (GSHP) and a Radiant Floor (RF) was simulated and calibrated using TRNSYS and GenOpt. The results demonstrated that this new multi-stage procedure met the ASHRAE standards and achieved better results than those obtained with a global calibration. The Mean Bias Error (MBE) and the Coefficient of Variation of the Root Mean Square Error (CV(RMSE)) of the hourly temperature data were reduced below 3.74% and 6.03% respectively, involving an improvement of approximately 50% over typical global calibration methods. (C) 2017 Elsevier B.V. All rights reserved.
引用
收藏
页码:182 / 199
页数:18
相关论文
共 40 条
[1]  
Agami Reddy T., 2006, ASHRAE T 1, V1, P226
[2]  
[Anonymous], 2005, 77302005 IOF STAND
[3]  
[Anonymous], 2002, MEAS EN DEM SAV
[4]  
[Anonymous], 2011, TESS COMP LIB GEN DE, P22
[5]   Experimental evaluation and dynamic simulation of a ground coupled heat pump for a commercial building [J].
Arteconi, Alessia ;
Brandoni, Caterina ;
Rossi, Guido ;
Polonara, Fabio .
INTERNATIONAL JOURNAL OF ENERGY RESEARCH, 2013, 37 (15) :1971-1980
[6]  
ASHRAE, 2001, 140 ASHRAE
[7]   Ground-coupled heat pumps: Part 1-Literature review and research challenges in modeling and optimal control [J].
Atam, Ercan ;
Helsen, Lieve .
RENEWABLE & SUSTAINABLE ENERGY REVIEWS, 2016, 54 :1653-1667
[8]   Semi-analytical model for geothermal borefields with independent inlet conditions [J].
Belzile, Patrick ;
Lamarche, Louis ;
Rousse, Daniel R. .
GEOTHERMICS, 2016, 60 :144-155
[9]   Calibrated simulation of a public library HVAC system with a ground-source heat pump and a radiant floor using TRNSYS and GenOpt [J].
Cacabelos, Anton ;
Eguia, Pablo ;
Luis Miguez, Jose ;
Granada, Enrique ;
Elena Arce, Maria .
ENERGY AND BUILDINGS, 2015, 108 :114-126
[10]   Efficiency of closed loop geothermal heat pumps: A sensitivity analysis [J].
Casasso, Alessandro ;
Sethi, Rajandrea .