A review and perspective on industry high-temperature heat pumps

被引:136
作者
Jiang, Jiatong [1 ]
Hu, Bin [1 ]
Wang, R. Z. [1 ]
Deng, Na [2 ]
Cao, Feng [3 ]
Wang, Chi-Chuan [4 ]
机构
[1] Shanghai Jiao Tong Univ, Res Ctr Solar Power & Refrigerat MOE China, Inst Refrigerat & Cryogen, Shanghai 200240, Peoples R China
[2] Tianjin Univ, Sch Environm Sci & Engn, Tianjin 300072, Peoples R China
[3] Xi An Jiao Tong Univ, Sch Energy & Power Engn, Xian 710049, Peoples R China
[4] Natl Yang Ming Chiao Tung Univ, Dept Mech Engn, Hsinchu 300, Taiwan
基金
中国国家自然科学基金;
关键词
High-temperature heat pump; Low-GWP refrigerants; Industrial heating; Carbon neutral; EXERGY ANALYSIS; WORKING FLUID; WATER; CO2; PERFORMANCE; REFRIGERANTS; RECOVERY; SYSTEMS; HCFO-1224YD(Z); SIMULATION;
D O I
10.1016/j.rser.2022.112106
中图分类号
X [环境科学、安全科学];
学科分类号
08 ; 0830 ;
摘要
A reduction of CO2 emission from heating industry is urgently required due to the transition of industry towards carbon neutrality. The High-temperature Heat Pump (HTHP) is a valid alternative technology for heating while enhancing energy utilization efficiency to potentially contribute to carbon neutral electrification. Therefore, this study proposes some future development directions for HTHPs based on the current state of research and application cases to accelerate the replacement of industrial boilers. The laboratory-scale HTHPs with heat sink temperature higher than 80 ? are reviewed following different configurations, including single-stage, multistage, cascade, hybrid system, etc. Among these experimental researches, about 71% of the prototypes were charged with low Global Warming Potential (GWP) refrigerants. Besides, HTHPs with large temperature lift is a must in practice, and some even achieved temperature lift above 100 ?. For the application researches, the heating capacity of reviewed HTHPs applied in industry ranged from 60 kW to 18 MW with output temperature higher than 80 C. High-GWP refrigerants, especially R245fa and R134a, are the mainstream refrigerants for applications until now, accounting for 67% of the reviewed cases. The remaining units were charged with natural refrigerants, and no reports are available for new synthetic refrigerant (e.g. HFOs, HCFOs). Based on the comprehensive review of HTHPs from laboratory and application, four suggestive prospects are revealed for HTHPs, being i) low-GWP refrigerants; ii) output temperature higher than 100 ?; iii) heating capacity larger than 1 MW; iv) Coefficient of Potential (COP) larger than 4 under 40 C temperature lift.
引用
收藏
页数:19
相关论文
共 120 条
[1]   THERMODYNAMIC AND ENVIRONMENTAL ANALYSIS OF A HIGH-TEMPERATURE HEAT PUMP USING HCFO-1224YD(Z) AND HCFO-1233ZD(E) [J].
Alhamid, Muhammad Idrus ;
Aisyah, Nyayu ;
Nasruddin ;
Lubis, Arnas .
INTERNATIONAL JOURNAL OF TECHNOLOGY, 2019, 10 (08) :1585-1592
[2]  
Annex 35 IEA, 2014, HPPAN351 ANN 35 IE 1
[3]  
[Anonymous], 2016, 14 S EN TU GRAZ 10 1
[4]  
[Anonymous], 2020, WORLD CHIN EN OUTL 2
[5]  
[Anonymous], 2020, 2018 China's annual development report on building energy efficiency
[6]  
Arpagaus C., 2019, 2 C HIGH TEMP HEAT P
[7]  
Arpagaus C, 2019, 25 IIR INT C REFR IC
[8]   High temperature heat pumps: Market overview, state of the art, research status, refrigerants, and application potentials [J].
Arpagaus, Cordin ;
Bless, Frederic ;
Uhlmann, Michael ;
Schiffmann, Jurg ;
Bertsch, Stefan S. .
ENERGY, 2018, 152 :985-1010
[9]   A chronological review of advances in solar assisted heat pump technology in 21st century [J].
Badiei, A. ;
Akhlaghi, Y. Golizadeh ;
Zhao, X. ;
Shittu, S. ;
Xiao, X. ;
Li, J. ;
Fan, Y. ;
Li, G. .
RENEWABLE & SUSTAINABLE ENERGY REVIEWS, 2020, 132
[10]  
Bamigbetan O, 2017, INT WORKSH HIGH TEMP