Performance Assessment of a Refrigeration System Charged with Different Refrigerants Using Infrared Image Processing Techniques

被引:1
作者
Katircioglu, Ferzan [1 ]
Cingiz, Zafer [2 ]
Cay, Yusuf [3 ]
Gurel, Ali Etem [4 ]
Kolip, Ahmet [3 ]
机构
[1] Duzce Univ, Duzce Vocat Sch, Dept Elect & Automat, Duzce, Turkey
[2] Duzce Univ, Duzce Vocat Sch, Dept Elect & Energy, Duzce, Turkey
[3] Sakarya Univ Appl Sci, Fac Technol, Dept Mech Engn, Sakarya, Turkey
[4] Duzce Univ, Fac Engn, Dept Mech Engn, Duzce, Turkey
关键词
Ozone depletion potential (ODP); Global warming potential (GWP); Infrared image processing; Pearson's correlation similarity analysis; Coefficient of performance (COP); THERMOGRAPHY;
D O I
10.1007/s13369-021-05794-2
中图分类号
O [数理科学和化学]; P [天文学、地球科学]; Q [生物科学]; N [自然科学总论];
学科分类号
07 ; 0710 ; 09 ;
摘要
This study aims to investigate the performance of R417A, R422A, R422D and R438A refrigerants as alternatives to R22, in a commercial type refrigeration system operating with R22 refrigerant. To this end, first of all, the cooling capacity and coefficient of performance (COP) values were calculated for all refrigerants used in the experimental setup. Then, two methods were proposed, Pearson's Correlation Similarity Analysis (PCSA) and surface temperature-based COP (COPST), to evaluate the success of each alternative refrigerants, and R22 with infrared image analysis, separately. The COP values obtained for the refrigerants with the mathematical method are R22 4.07, R438A 3.88, R417A 3.63, R422D 3.37, and R422A 3.18, respectively. Both the COP values and the PCSA values (R438A 0.9425, R417A 0.9343, R422D 0.9167 and R422A 0.9080) show the proximity between the R22 refrigerant and other refrigerants. Similarly, the COPST method revealed the values of R22 6.8865, R438A 5.9539, R417A 5.3273, R422D 4.9898 and R422A 4.3057, and the fact that it has the same order with the other two methods demonstrates its operability in the performance test application with the developed infrared image processing. The compatibility of the order in the experimental results obtained from the PCSA and COPST methods and the COP calculation method and has proved that thanks to infrared imaging, the remote performance analysis of the refrigeration system can be successfully performed.
引用
收藏
页码:12009 / 12028
页数:20
相关论文
共 41 条
[1]   Requirements for a cocitation similarity measure, with special reference to Pearson's correlation coefficient [J].
Ahlgren, P ;
Jarneving, B ;
Rousseau, R .
JOURNAL OF THE AMERICAN SOCIETY FOR INFORMATION SCIENCE AND TECHNOLOGY, 2003, 54 (06) :550-560
[2]   Thermographic study of energetic installations [J].
Al-Kassir, AR ;
Fernandez, J ;
Tinaut, FV ;
Castro, F .
APPLIED THERMAL ENGINEERING, 2005, 25 (2-3) :183-190
[3]  
Allgood C.C., 2010, INT REFR AIR COND C, P1
[4]  
[Anonymous], 2020, CLIMALIFE IDS REFRIG
[5]   Experimental comparison of R22 with R417A performance in a vapour compression refrigeration plant subjected to a cold store [J].
Aprea, C ;
Renno, C .
ENERGY CONVERSION AND MANAGEMENT, 2004, 45 (11-12) :1807-1819
[6]   Infrared thermography for building diagnostics [J].
Balaras, CA ;
Argiriou, AA .
ENERGY AND BUILDINGS, 2002, 34 (02) :171-183
[7]   An entropy-based approach to automatic image segmentation of satellite images [J].
Barbieri, Andre L. ;
de Arruda, G. F. ;
Rodrigues, Francisco A. ;
Bruno, Odemir M. ;
Costa, Luciano da Fontoura .
PHYSICA A-STATISTICAL MECHANICS AND ITS APPLICATIONS, 2011, 390 (03) :512-518
[8]  
Bock Compressor, 2020, BOCK COMPR ALT REFR
[9]   Experimental investigation of a flat plate heat pipe performance using IR thermal imaging camera [J].
Boukhanouf, R. ;
Haddad, A. ;
North, M. T. ;
Buffone, C. .
APPLIED THERMAL ENGINEERING, 2006, 26 (17-18) :2148-2156
[10]  
Burch S, 1994, VEH THERM MAN SYST C