Design and Implementation of Lighting Control System Using Battery-Less Wireless Human Detection Sensor Networks

被引:6
作者
Yu, Tao [1 ]
Kuki, Yusuke
Matsushita, Gento [3 ]
Maehara, Daiki [2 ]
Sampei, Seiichi [4 ]
Sakaguchi, Kei [2 ]
机构
[1] Tokyo Inst Technol, Dept Elect & Elect Engn, Tokyo 1528550, Japan
[2] Tokyo Inst Technol, Tokyo 1528550, Japan
[3] Osaka Univ, Suita, Osaka 5650871, Japan
[4] Osaka Univ, Dept Informat & Commun Technol, Suita, Osaka 5650871, Japan
基金
日本学术振兴会;
关键词
proof-of-concept; energy saving; LED light control; battery less wireless human detection sensor network; multi-sensor user localization;
D O I
10.1587/transcom.2016EBP3344
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
Artificial lighting is responsible for a large portion of total energy consumption and has great potential for energy saving. This paper designs an LED light control algorithm based on users' localization using multiple battery-less binary human detection sensors. The proposed lighting control system focuses on reducing office lighting energy consumption and satisfying users' illumination requirement. Most current lighting control systems use infrared human detection sensors, but the poor detection probability, especially for a static user, makes it difficult to realize comfortable and effective lighting control. To improve the detection probability of each sensor, we proposed to locate sensors as close to each user as possible by using a battery-less wireless sensor network, in which all sensors can be placed freely in the space with high energy stability. We also proposed to use a multi-sensor-based user localization algorithm to capture user's position more accurately and realize fine lighting control which works even with static users. The system is actually implemented in an indoor office environment in a pilot project. A verification experiment is conducted by measuring the practical illumination and power consumption. The performance agrees with design expectations. It shows that the proposed LED lighting control system reduces the energy consumption significantly, 57% compared to the batch control scheme, and satisfies user's illumination requirement with 100010 probability.
引用
收藏
页码:974 / 985
页数:12
相关论文
共 32 条
  • [1] [Anonymous], 802154G IEEE
  • [2] [Anonymous], 62386 IEC
  • [3] [Anonymous], THESIS
  • [4] [Anonymous], Z91102011 JIS
  • [5] [Anonymous], 60929 IEC
  • [6] [Anonymous], IEICE TECHNICAL REPO
  • [7] [Anonymous], EL SAV POT LED LIGHT
  • [8] [Anonymous], P ACM ICUIMC 2012 FE
  • [9] [Anonymous], ENERGY BUILD
  • [10] Boyce P.R., 2003, HUMAN FACTORS LIGHTI