Operational control of an integrated drum boiler of a coal fired thermal power plant

被引:17
作者
Chandrasekharan, Sreepradha [1 ]
Panda, Rames C. [1 ]
Swaminathan, Bhuvaneswari Natrajan [2 ]
Panda, Atanu [3 ]
机构
[1] CSIR CLRI, Dept Chem Engn, Madras 600020, Tamil Nadu, India
[2] GKM Engg Coll, Elect & Instrumentat, Madras 600089, Tamil Nadu, India
[3] Inst Engn & Management, Kolkata, India
关键词
Mathematical modeling; Process control; Subcritical drum boiler; Inverse decoupling; Thermal power plant; Parameter identification; CONTROL-SYSTEM-DESIGN; RANGE PREDICTIVE CONTROL; TURBINE SYSTEM; MODEL; VALIDATION; SIMULATION; STRATEGY;
D O I
10.1016/j.energy.2018.06.157
中图分类号
O414.1 [热力学];
学科分类号
摘要
Boiler in thermal-power-plant plays important role in generation of power. Conventional subcriticalboilers use single-loop controls which are less efficient. An effective control of temperature and pressure of boiler is necessary to enable safe power generation. This article discusses application of three different multivariable-control strategies, namely, PID (Proportional-Integral- Derivative), MAC (Model Predictive Controller) and Inverse-decoupling-control to the individual units of boiler (economizer, drum, super-heater) as well as to the integrated boiler unit of the coal-fired thermal-power-plant separately. The mathematical-model derived based on mass-balance and energy-balance equations of economizer, drum and superheater units are used for the synthesis of controller. The non-square nature of mathematical-model carries complexity in the design of controllers. The performances, based on minimization of objective-function containing closed-loop error along with the control-effort of individual and integrated units, of the boiler using IMC (Internal-Model-Control) based PID, Inversedecouple and MPC in the presence of disturbances are analyzed and compared. The results show that multi-loop control of integrated units ensures asymptotic-stability compared to unstable single-loop control and the controller needs to take less effort in the case of the integrated unit compared to the individual units. The results suggest for implementation of integrated multi-loop control instead of controlling individual boiler units. (C) 2018 Elsevier Ltd. All rights reserved.
引用
收藏
页码:977 / 987
页数:11
相关论文
共 35 条
[31]   Mathematical modeling, simulation and validation of a boiler drum: Some investigations [J].
Sunil, P. U. ;
Barve, Jayesh ;
Nataraj, P. S. V. .
ENERGY, 2017, 126 :312-325
[32]   Inverted decoupling: a neglected technique [J].
Wade, HL .
ISA TRANSACTIONS, 1997, 36 (01) :3-10
[33]   Decoupling Revisited [J].
Waller, M ;
Waller, JB ;
Waller, KV .
INDUSTRIAL & ENGINEERING CHEMISTRY RESEARCH, 2003, 42 (20) :4575-4577
[34]   Data-Driven Modeling and Predictive Control for Boiler-Turbine Unit [J].
Wu, Xiao ;
Shen, Jiong ;
Li, Yiguo ;
Lee, Kwang Y. .
IEEE TRANSACTIONS ON ENERGY CONVERSION, 2013, 28 (03) :470-481
[35]  
Zheng Q, 2011, P 30 CHIN CONTR C 22