Smart Impedance: A New Way to Look at Hybrid Filters

被引:55
作者
Gonzatti, Robson B. [1 ]
Ferreira, Silvia Costa [1 ]
da Silva, Carlos Henrique [2 ]
Pereira, Rondineli Rodrigues [1 ]
Borges da Silva, Luiz Eduardo [1 ]
Lambert-Torres, Germano [3 ]
机构
[1] Univ Fed Itajuba, BR-37500903 Itajuba, Brazil
[2] Univ Fed Ouro Preto, BR-35931008 Joao Monlevade, Brazil
[3] PS Solut, BR-37500005 Itajuba, Brazil
关键词
Active impedance; harmonic compensation; hybrid filter; proportional resonant (P plus Resonant) controller; smart impedance; ACTIVE POWER FILTER; HARMONIC COMPENSATION; PERFORMANCE; GENERATION; CONTROLLER; SYSTEMS;
D O I
10.1109/TSG.2015.2466613
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
Smart impedance is a new way to look at hybrid active power filters. As originally proposed in the literature, hybrid active filters were presented to improve the physical limitation of tuned passive filters. A new conditioner named smart impedance is proposed to eliminate the need of passive filter tuning procedure, the whole tuning process is performed electronically. The proposed topology is able to manipulate the displacement power factor and perform multiple frequency harmonic current mitigation at the same time. In weak systems, where the source impedance is not negligible, like in smart grids, smart impedance guaranties the voltage regulation and stability. The smart impedance control strategy uses proportional resonant controller, which allows phase-locked loop-less power system synchronization. Smart impedance system is composed of an active converter, a coupling transformer, and a capacitive unit, arranged as three phase or single phase equipment.
引用
收藏
页码:837 / 846
页数:10
相关论文
共 29 条
[1]   Active Power Filter Control Strategy With Implicit Closed-Loop Current Control and Resonant Controller [J].
Angulo, Mauricio ;
Ruiz-Caballero, Domingo A. ;
Lago, Jackson ;
Heldwein, Marcelo Lobo ;
Mussa, Samir Ahmad .
IEEE TRANSACTIONS ON INDUSTRIAL ELECTRONICS, 2013, 60 (07) :2721-2730
[2]   Hybrid solutions for improving passive filter performance in high power applications [J].
Bhattacharya, S ;
Cheng, PT ;
Divan, DM .
IEEE TRANSACTIONS ON INDUSTRY APPLICATIONS, 1997, 33 (03) :732-747
[3]   Operations of the Dominant Harmonic Active Filter (DHAF) under realistic utility conditions [J].
Cheng, PT ;
Bhattacharya, S ;
Divan, D .
IEEE TRANSACTIONS ON INDUSTRY APPLICATIONS, 2001, 37 (04) :1037-1044
[4]  
da Silva CH, 2012, IEEE IND ELEC, P1416, DOI 10.1109/IECON.2012.6388565
[5]   A Digital PLL Scheme for Three-Phase System Using Modified Synchronous Reference Frame [J].
da Silva, Carlos Henrique ;
Pereira, Rondineli Rodrigues ;
Borges da Silva, Luiz Eduardo ;
Lambert-Torres, Germano ;
Bose, Bimal K. ;
Ahn, Se Un .
IEEE TRANSACTIONS ON INDUSTRIAL ELECTRONICS, 2010, 57 (11) :3814-3821
[6]   Voltage/VAR Control in Distribution Networks via Reactive Power Injection Through Distributed Generators [J].
Deshmukh, Siddharth ;
Natarajan, Balasubramaniam ;
Pahwa, Anil .
IEEE TRANSACTIONS ON SMART GRID, 2012, 3 (03) :1226-1234
[7]   Hybrid Power Filter to Enhance Power Quality in a Medium-Voltage Distribution Network [J].
Fabian Corasaniti, Victor ;
Beatriz Barbieri, Maria ;
Liliana Arnera, Patricia ;
Ines Valla, Maria .
IEEE TRANSACTIONS ON INDUSTRIAL ELECTRONICS, 2009, 56 (08) :2885-2893
[8]  
Ferreira SC, 2013, IEEE ENER CONV, P2264, DOI 10.1109/ECCE.2013.6646989
[9]   A PRACTICAL APPROACH TO HARMONIC COMPENSATION IN POWER-SYSTEMS - SERIES CONNECTION OF PASSIVE AND ACTIVE-FILTERS [J].
FUJITA, H ;
AKAGI, H .
IEEE TRANSACTIONS ON INDUSTRY APPLICATIONS, 1991, 27 (06) :1020-1025
[10]   A hybrid active filter for damping of harmonic resonance in industrial power systems [J].
Fujita, H ;
Yamasaki, T ;
Akagi, H .
IEEE TRANSACTIONS ON POWER ELECTRONICS, 2000, 15 (02) :215-222