An improved control method of fault ride-through for DPMWT-based wind farm considering coupling effect of HVDC transmission system

被引:5
作者
Ouyang, Jinxin [1 ]
Yu, Jianfeng [1 ]
Pang, Mingyu [1 ]
Diao, Yanbo [2 ]
机构
[1] Chongqing Univ, Sch Elect Engn, State Key Lab Power Transmiss Equipment & Syst Sec, Peoples Republ China, Chongqing 400044, Peoples R China
[2] Chongqing City Management Coll, Chongqing, Peoples R China
基金
中国国家自然科学基金;
关键词
DPMWT; Wind farm; HVDC; Fault ride-through; Reactive power control; COMMUTATION FAILURE; CONTROL STRATEGY; VOLTAGE; PERFORMANCE; TURBINE; DESIGN;
D O I
10.1016/j.ijepes.2022.108064
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
With the continuous increase of wind power penetration, a large number of wind farm have been constructed. The large-scale wind farm is usually transmitted through high voltage direct current(HVDC) transmission system. The reactive power output on the grid-side converter is utilized to support grid voltage, which is a common method of fault ride-through for direct-drive permanent magnet synchronous generator-based wind turbine (DPMWT). The power control capability of DPMWT-based wind farm(DPMWF) is affected by safety constraints and operating characteristics of the external system. However, the control strategy of DPMWF cannot yet take into account the coupling effect of HVDC and may be difficult to meet the voltage recovery requirements of the grid during the grid fault. Even the DPMWT may oscillate due to the over-threshold of the control setting value. Therefore, a power coupling model between DPMWF and rectifier station of HVDC transmission system is established, and an evaluation method for the power controllability of DPMWF under fault considering the coupling effect of HVDC transmission system is proposed. A calculation method of maximum reference value of reactive power control of DPMWF based on model predictive control is proposed taking into account the con-verter constraints of DPMWF and the influence of the external system. An improved control method of fault ride-through is further proposed, which takes into account the coupling effect of HVDC transmission system. The simulation shows that the proposed method can improve the voltage recovery characteristics under the grid fault, effectively guarantee the fault ride-through of DPMWF.
引用
收藏
页数:8
相关论文
共 50 条
  • [21] Fault Ride-through Control Strategy of MMC-HVDC System Under Asymmetric Grid Conditions
    Yu J.
    Liu C.
    Wang J.
    Zhongguo Dianji Gongcheng Xuebao/Proceedings of the Chinese Society of Electrical Engineering, 2020, 40 (17): : 5653 - 5664
  • [22] A coordination control between energy storage based DVR and wind turbine for continuous fault ride-through
    Chen, Xunjun
    Geng, Guangchao
    Jiang, Quanyuan
    IET RENEWABLE POWER GENERATION, 2024, 18 (14) : 2560 - 2574
  • [23] A new fault ride-through control for DFIG-based wind energy systems
    Morshed, Mohammad Javad
    Fekih, Afef
    ELECTRIC POWER SYSTEMS RESEARCH, 2017, 146 : 258 - 269
  • [24] Fault Ride-Through Capability Enhancement of Type-4 WECS in Offshore Wind Farm via Nonlinear Adaptive Control of VSC-HVDC
    Sang, Yiyan
    Yang, Bo
    Shu, Hongchun
    An, Na
    Zeng, Fang
    Yu, Tao
    PROCESSES, 2019, 7 (08)
  • [25] Zero DC Voltage Control Based DC Fault Ride-Through Strategy for Hybrid Modular Multilevel Converter in HVDC
    Yin T.
    Wang Y.
    Duan G.
    Liu G.
    Hu S.
    Diangong Jishu Xuebao/Transactions of China Electrotechnical Society, 2019, 34 : 343 - 351
  • [26] Fault Ride-Through and Power Smoothing Control of PMSG-Based Wind Generation Using Supercapacitor Energy Storage System
    Worku, Muhammed Y.
    Abido, M. A.
    ARABIAN JOURNAL FOR SCIENCE AND ENGINEERING, 2019, 44 (03) : 2067 - 2078
  • [27] An Improved Fault Ride Through Scheme and Control Strategy for DFIG-Based Wind Energy Systems
    Musarrat, Md Nafiz
    Fekih, Afef
    Islam, Md Rabiul
    IEEE TRANSACTIONS ON APPLIED SUPERCONDUCTIVITY, 2021, 31 (08)
  • [28] Fault Ride-through Technology of Hybrid HVDC Wind Power System Based on Multi-phase Permanent Magnet Synchronous Generator
    Liu Y.
    Zeng X.
    Luo Y.
    Zhang S.
    Wei M.
    Dianli Xitong Zidonghua/Automation of Electric Power Systems, 2020, 44 (08): : 133 - 140
  • [29] An Improved Frequency Modulation Method for Fault Ride Through of MMC-HVDC Systems Connected DFIG Wind Farms
    Li, Yutong
    Zhu, Meng
    Chao, P.
    Li, W.
    Sun, Bing
    2018 2ND IEEE CONFERENCE ON ENERGY INTERNET AND ENERGY SYSTEM INTEGRATION (EI2), 2018,
  • [30] Continuous Fault Ride-through Control of Wind Turbine Using Energy Storage Based DVR
    Chen, Xunjun
    Geng, Guangchao
    Jiang, Quanyuan
    2023 IEEE/IAS INDUSTRIAL AND COMMERCIAL POWER SYSTEM ASIA, I&CPS ASIA, 2023, : 1576 - 1580