Simulation Research of the Unbalanced Factor under the Mutual Influence of the Multi Voltage Level Quadruple-Circuit Sharing the Same Tower

被引:0
|
作者
Liang, Haisheng [1 ]
Zhu, Chaojie [1 ]
Li, Xiaorong [2 ]
Zhang, Xuhang [1 ]
Cao, Wei [2 ]
机构
[1] State Grid Shanghai Econ Res Inst, Shanghai, Peoples R China
[2] Shanghai Univ Elect Power, Shanghai, Peoples R China
关键词
extra high voltage (EHV); mixed-voltage; quadruple-circuit; electric unbalanced factor;
D O I
暂无
中图分类号
X [环境科学、安全科学];
学科分类号
08 ; 0830 ;
摘要
The electric unbalanced factor of a real quadruple-circuit transmission lines with 220 kV/1000 kV and 220 kV/500kV on the same tower in different sections is simulated by Electro-Magnetic Transient Program(EMTP). The simulation indicates that the current unbalanced factor of 220kV transmission lines is affected by the service conditions of 1000kV and 500kV lines, and that of 500kV transmission lines is also influenced by 1000kV transmission lines through 220kV lines. To reduce the electric unbalanced factor, the reverse phase sequence arrangement of double-circuit 220kV lines is recommended.
引用
收藏
页码:144 / 150
页数:7
相关论文
共 8 条
  • [1] Simulation analysis on electromagnetic environment of quadruple-circuit transmission lines belonging to different voltage classes on the same tower
    Zhang, Xiao
    Jia, Zhen-Hong
    Wu, Suo-Ping
    Wu, Jian-Hong
    Wang, Jian-Min
    Chen, Guang
    Zhou, Hao
    Dianwang Jishu/Power System Technology, 2010, 34 (05): : 207 - 211
  • [2] Cross-voltage short-circuit calculation for mixed-voltage quadruple-circuit lines on the same tower
    Zheng, Tao
    Zhang, Jiaqin
    Wu, Dan
    Huang, Shaofeng
    Wang, Xiaoli
    IET GENERATION TRANSMISSION & DISTRIBUTION, 2017, 11 (09) : 2342 - 2350
  • [3] Electromagnetic environment influence factors of quadruple-circuit transmission line with 1 000 kV/500 kV dual voltage on the same tower and optimization measures analysis
    Huang, Xueliang
    Wang, Yu
    Wen, Feng
    Gaodianya Jishu/High Voltage Engineering, 2015, 41 (11): : 3642 - 3650
  • [4] Secure Distance of the Quadruple-circuit Transmission Line with Dual Voltage 220kV/110kV on the Same Tower Passing Over or Close to Building
    Zhu, He
    Xu, Datian
    Zhao, Haoran
    2015 3RD ASIAN PACIFIC CONFERENCE ON MECHATRONICS AND CONTROL EINGINEERING (APCMCE 2015), 2015, : 29 - 39
  • [5] Research on Lightning Performance of Quadruple Circuit Transmission Line with Dual Voltage 500/220-kV on the Same Tower
    Li Xiaolan
    Du Zhongdong
    Wen Jiqun
    Chen Jiahong
    Gu Shanqiang
    2011 ASIA-PACIFIC POWER AND ENERGY ENGINEERING CONFERENCE (APPEEC), 2011,
  • [6] Lightning performance of quadruple circuit transmission line with Voltage 500 kV on the same vertical tower under unbalance insulation
    Su, Fei
    Zhou, Hao
    Zhao, Bincai
    Gaodianya Jishu/High Voltage Engineering, 2012, 38 (09): : 2473 - 2480
  • [7] Research on the passing ability simulation of waterway under the influence of multi-factor compounding
    Liu, Xin
    Zhang, Qingfa
    Zhang, Tengwen
    Shang, Hongyue
    2024 4TH INTERNATIONAL CONFERENCE ON MACHINE LEARNING AND INTELLIGENT SYSTEMS ENGINEERING, MLISE 2024, 2024, : 334 - 337
  • [8] Influence of zero-sequence mutual inductance on earth-fault distance protection for four-circuit transmission lines belonging to different voltage classes on same tower under different operation modes
    Zhao, Kaichao
    Zhou, Zexin
    Du, Dingxiang
    Dianwang Jishu/Power System Technology, 2010, 34 (12): : 193 - 197