Fault Characteristic and Low Voltage Ride-Through Requirements Applicability Analysis for a Permanent Magnet Synchronous Generator-Based Wind Farm

被引:8
作者
Chen, Wei [1 ,2 ]
Zheng, Taiying [1 ,2 ]
Han, Junfei [3 ]
机构
[1] Zhejiang Univ, Coll Elect Engn, Hangzhou 310027, Zhejiang, Peoples R China
[2] Zhejiang Univ, Zhejiang Prov Key Lab Elect Machine Syst, Hangzhou 310027, Zhejiang, Peoples R China
[3] Inner Mongolia Power Grp Co Ltd, Inner Mongolia Elect Power Sci & Res Inst, Hohhot 010020, Peoples R China
基金
中国国家自然科学基金;
关键词
permanent magnet synchronous generator; wind farm; fault characteristic analysis; low voltage ride-through; applicability analysis; grid code; POWER; TURBINE; PROTECTION; OPERATION; DIAGNOSIS; TRACKING; SYSTEM;
D O I
10.3390/en12173400
中图分类号
TE [石油、天然气工业]; TK [能源与动力工程];
学科分类号
0807 ; 0820 ;
摘要
As the penetration of wind energy is being dramatically increased, the impact of wind energy on the power system should be roundly studied, especially for the fault characteristics analysis and applicability analysis of low voltage ride-through (LVRT) requirements for a whole wind farm (WF) and an individual wind turbine generator (WTG). This paper firstly describes a detailed modeling of a permanent magnet synchronous generator (PMSG)-based WF and analyzes the fault characteristics of the WF under various fault conditions. The validation of the fault characteristics analysis is carried out with the EMTP-RV generated data, with the consideration of different fault positions, fault types, and wind speeds. The relay protection and the related grid code are also taken into account. In addition, the applicability analysis of LVRT requirements for a WF and a WTG is also implemented, from the points of minimal grid-connection time and minimal dynamic reactive current support ability. The fault characteristic analysis of a PMSG-based WF could be helpful for developing new control or protection methods for a PMSG-based WF. Meanwhile, the applicability analysis of LVRT requirements could serve as a reference for WTG manufacturers, WF administrators, and grid operator.
引用
收藏
页数:34
相关论文
共 39 条
[1]  
Abo-Khalil A.G., 2006, P 2006 37 IEEE POW E
[2]  
[Anonymous], 2012, 199632011 PRC GBT
[3]  
[Anonymous], 2019, 369952018 PRCGBT
[4]  
[Anonymous], IEEE CAN EL POW C 20
[5]  
Boersma S, 2017, P AMER CONTR CONF, P1, DOI 10.23919/ACC.2017.7962923
[6]  
Cai X., 2006, DYNAMIC MODELING WIN, P240
[7]   Fault ride-through of large wind farms using series dynamic braking resistors (March 2007) [J].
Causebrook, Andrew ;
Atkinson, David J. ;
Jack, Alan G. .
IEEE TRANSACTIONS ON POWER SYSTEMS, 2007, 22 (03) :966-975
[8]   Control of permanent-magnet generators applied to variable-speed wind-energy systems connected to the grid [J].
Chinchilla, M ;
Arnaltes, S ;
Burgos, JC .
IEEE TRANSACTIONS ON ENERGY CONVERSION, 2006, 21 (01) :130-135
[9]   A phase tracking system for three phase utility interface inverters [J].
Chung, SK .
IEEE TRANSACTIONS ON POWER ELECTRONICS, 2000, 15 (03) :431-438
[10]   Low-voltage ride-through of a full converter wind turbine with permanent magnet generator [J].
Conroy, J. F. ;
Watson, R. .
IET RENEWABLE POWER GENERATION, 2007, 1 (03) :182-189