High-temperature ampacity model for overhead conductors

被引:20
|
作者
Chen, SL [1 ]
Black, WZ
Loard, HW
机构
[1] Cordis Corp, Miami Lakes, FL 33014 USA
[2] Georgia Inst Technol, Sch Mech Engn, Atlanta, GA 30332 USA
[3] Georgia Power Co, Line Design, Atlanta, GA 30297 USA
关键词
ampacity; heat transfer; high-temperature operation; overhead lines;
D O I
10.1109/TPWRD.2002.804003
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
A computer-based ampacity model that can predict the temperature of overhead conductors for temperatures as high as 250 degreesC has been developed. The model is a revision of a program that has been reliably used for approximately 20 years to calculate the transient ampacity of a wide variety of conductor designs. The accuracy of the program has been determined by comparing the program predictions with temperatures that are measured on a full-scale energized outdoor test span. The accuracy of the program decreases as the average conductor temperature increases. As the conductor temperature increases, the spatial variations, both azimuthal and radial, are magnified and the task of calculating a single, average conductor temperature becomes more challenging. Typical variations in the conductor temperature were as high as 65 degreesC in a single span when the conductor temperature approached 250 degreesC. These temperature variations create difficulties when trying to either measure the conductor temperature with hardware attached to the line or predict the temperature with a computer-based ampacity model.
引用
收藏
页码:1136 / 1141
页数:6
相关论文
共 50 条
  • [1] High-temperature sag model for overhead conductors
    Chen, SL
    Black, WZ
    Fancher, ML
    IEEE TRANSACTIONS ON POWER DELIVERY, 2003, 18 (01) : 183 - 188
  • [2] Possibilities of Increasing the Ampacity of Overhead Lines Using High-Temperature Low-Sag Conductors in the Electric Power System of the Slovak Republic
    Margita, Frantisek
    Bena, Lubomir
    Malska, Wieslawa
    Pijarski, Pawel
    APPLIED SCIENCES-BASEL, 2024, 14 (17):
  • [3] INCREASING OF TRANSMISSION ABILITY AT HIGH VOLTAGE OVERHEAD LINES AMPACITY MODEL
    Vostracky, Zdenek
    Piclova, Petra
    Polivka, Jiri
    Snajdr, Jaroslav
    Krutina, Ales
    PROCEEDINGS OF THE 12TH INTERNATIONAL SCIENTIFIC CONFERENCE ELECTRIC POWER ENGINEERING 2011, 2011, : 53 - 56
  • [4] New Approach for Ampacity Calculation of Overhead Lines With Steel-Cored Conductors
    Meyberg, Ruyguara A.
    de Barros, Maria Teresa Correia
    Lima, Antonio C. S.
    IEEE TRANSACTIONS ON POWER DELIVERY, 2023, 38 (02) : 1011 - 1019
  • [5] Evaluation of theoretical results of overhead line ampacity model
    Snajdr, Jaroslav
    Vostracky, Zdenek
    Sedlacek, Jan
    PROCEEDINGS OF THE 7TH INTERNATIONAL SCIENTIFIC SYMPOSIUM ON ELECTRICAL POWER ENGINEERING (ELEKTROENERGETIKA 2013), 2013, : 152 - 154
  • [6] Tension and Ampacity Monitoring System for Overhead Lines
    Albizu, Igor
    Fernandez, Elvira
    Eguia, Pablo
    Torres, Esther
    Javier Mazon, Angel
    IEEE TRANSACTIONS ON POWER DELIVERY, 2013, 28 (01) : 3 - 10
  • [7] Analysis of current ampacity of the 110 kV overhead transmission line using a multiple regression model
    Malska, Wiesawa
    ELECTRIC POWER SYSTEMS RESEARCH, 2024, 236
  • [8] Infrared Temperature Measurement Sensors of Overhead Power Conductors
    Castro, Pablo
    Lecuna, Ramon
    Manana, Mario
    Martin, Maria Jose
    Campo, Dolores del
    SENSORS, 2020, 20 (24) : 1 - 13
  • [9] Temperature profile of progressive damaged overhead electrical conductors
    Cimini, Carlos Alberto, Jr.
    Araujo Fonseca, Beline Quintino
    INTERNATIONAL JOURNAL OF ELECTRICAL POWER & ENERGY SYSTEMS, 2013, 49 : 280 - 286
  • [10] Experimental Study of Dynamic Line Rating Applied to High-Temperature Low-Sag Conductors
    Vejo, Luis
    Castro, Pablo
    Manana, Mario
    Laso, Alberto
    Lecuna, Ramon
    Bustamante, Sergio
    Sainz, Eugenio
    ENERGIES, 2025, 18 (04)