Study on thermal pressure in a sloping underground tunnel under natural ventilation

被引:39
作者
Li, Angui [1 ]
Gao, Xiaopan [1 ]
Ren, Tong [1 ]
机构
[1] Xian Univ Architecture & Technol, Sch Environm & Municipal Engn, Xian 710055, Shaanxi, Peoples R China
基金
美国国家科学基金会;
关键词
Natural ventilation; Temperature distribution; Thermal pressure; Sloping underground tunnel; AIR HEAT-EXCHANGERS; ANALYTICAL-MODEL; EARTH; FIRE; PERFORMANCE; SYSTEMS; FLOW; TEMPERATURE; BUILDINGS;
D O I
10.1016/j.enbuild.2017.04.060
中图分类号
TU [建筑科学];
学科分类号
0813 ;
摘要
Tunnels are of key importance to the ventilation network in underground buildings. For sloping tunnels, the effect of thermal pressure on the underground ventilation system has not been clarified in the existing research. A field test in an underground sloping tunnel was carried out and the results showed that the temperature decreases in the form of exponent. Based on an exponential model of temperature decrease, an equation to predict thermal pressure is proposed for sloping underground tunnels. Four factors on the thermal pressure, surface roughness of the tunnel wall, air velocity, dimensions of the underground tunnel and temperature difference between the air and the tunnel wall are discussed in detail. Surface roughness of the tunnel wall, air velocity and dimensions of the tunnel have been found having little impact on the thermal pressure efficiency when the tunnel is beyond the length of Linin. The temperature difference between the air and the tunnel wall is the main factor on the thermal pressure efficiency. A simplified method is recommended to calculate the thermal pressure for sloping underground tunnels. (C) 2017 Elsevier B.V. All rights reserved.
引用
收藏
页码:200 / 209
页数:10
相关论文
共 45 条
  • [1] A'zami A., 2005, Passive and Low Energy Cooling for the Built Environment, P1021
  • [2] AI-Ajmi F, 2006, BUILD ENVIRON, V41, P235
  • [3] [Anonymous], WIND CHIMNEY INTEGRA
  • [4] Bailey JL, 2002, FIRE PROTECT ENG, V12, P139
  • [5] Experimental and analytical studies of earth-air heat exchanger (EAHE) systems in India: A review
    Bisoniya, Trilok Singh
    Kumar, Anil
    Baredar, Prashant
    [J]. RENEWABLE & SUSTAINABLE ENERGY REVIEWS, 2013, 19 : 238 - 246
  • [6] Bush A.W., 1975, HEAT TRANSFER JAMES
  • [7] Chen Qigao, 2004, AIRFLOW MEASUREMENT
  • [8] A study on tilted tunnel fire under natural ventilation
    Chow, W. K.
    Gao, Y.
    Zhao, J. H.
    Dang, J. F.
    Chow, Nadia C. L.
    [J]. FIRE SAFETY JOURNAL, 2016, 81 : 44 - 57
  • [9] Ciampi M., 1970, WIT T ECOL ENV, P62
  • [10] A one-dimensional transient analytical model for earth-to-air heat exchangers, taking into account condensation phenomena and thermal perturbation from the upper free surface as well as around the buried pipes
    Cucumo, M.
    Cucumo, S.
    Montoro, L.
    Vulcano, A.