In this study, the performance of a split-type air conditioner with evaporatively-cooled condenser was examined. The effect of evaporative cooling of the condenser on the performance parameters and energy efficiency were determined by comparing the results from an air conditioner with conventional type aircooled condenser. Both systems were tested simultaneously for different ambient conditions. An optimization study were also performed to find out the optimal climatic conditions for the proposed system. The effects of outdoor temperature and relative humidity on both total power consumption and COP were discussed. With the evaporative cooling of the condenser of the split-type air conditioner, the COP increased by 10.2%-35.3%, and the cooling capacity increased by 5.8%-18.6%, while the total power consumption decreased by 4%-12.4%. The results showed that the outdoor relative humidity and temperature had a significant influence on the COP, cooling capacity, and total power input for split-type air conditioners with an evaporative condenser. The results of the optimization study showed that the optimal condition maximizing the COP of the proposed system was confirmed as higher outdoor temperature and lower relative humidity. For the total power consumption, however, the optimal condition was found as medium levels of the temperature and humidity. The effect of the outdoor temperature on the electricity consumption is larger than that of the RH, and this provides an opportunity of using the proposed system in a wide-range climatic conditions.(c) 2021 Karabuk University. Publishing services by Elsevier B.V. This is an open access article under the CC BY-NC-ND license (http://creativecommons.org/licenses/by-nc-nd/4.0/).
引用
收藏
页数:10
相关论文
共 36 条
[1]   Consolidated experimental heat and mass transfer database for a reduced scale evaporative condenser [J].
Acunha Junior, Ivoni Carlos ;
Smith-Schneider, Paulo .
INTERNATIONAL JOURNAL OF REFRIGERATION-REVUE INTERNATIONALE DU FROID, 2016, 66 :21-31
[2]   Experimental evaluation of one, two, and three stage evaporative cooling systems [J].
Al-Juwayhel, F ;
El-Dessouky, H ;
Ettouney, H ;
Al-Qattan, M .
HEAT TRANSFER ENGINEERING, 2004, 25 (06) :72-86
[3]  
Alam Z, 2020, INT J ENERGY CLEAN E, V21, DOI [10.1615/InterJEnerCleanEnv.2020029330, DOI 10.1615/INTERJENERCLEANENV.2020029330]
[4]  
ASHRAE, 2007, 9012004 ASHRAE
[5]   Energetic and financial sustainability of solar assisted heat pump heating systems in Europe [J].
Bellos, Evangelos ;
Tzivanidis, Christos .
SUSTAINABLE CITIES AND SOCIETY, 2017, 33 :70-84
[6]   Numerical modeling of rigid media evaporative cooler [J].
Beshkani, A ;
Hosseini, R .
APPLIED THERMAL ENGINEERING, 2006, 26 (5-6) :636-643
[7]   Performance analysis of a solar-assisted heat pump with an evacuated tubular collector for domestic heating [J].
Caglar, Ahmet ;
Yamali, Cemil .
ENERGY AND BUILDINGS, 2012, 54 :22-28
[8]   Energy saving potential of an indirect evaporative cooler as a pre-cooling unit for mechanical cooling systems in Iran [J].
Delfani, Shahram ;
Esmaeelian, Jafar ;
Pasdarshahri, Hadi ;
Karami, Maryam .
ENERGY AND BUILDINGS, 2010, 42 (11) :2169-2176
[9]   Performance analysis of two-stage evaporative coolers [J].
El-Dessouky, H ;
Ettouney, H ;
Al-Zeefari, A .
CHEMICAL ENGINEERING JOURNAL, 2004, 102 (03) :255-266
[10]   Comparative analysis of an evaporative condenser using artificial neural network and adaptive neuro-fuzzy inference system [J].
Ertunc, H. Metin ;
Hosoz, Murat .
INTERNATIONAL JOURNAL OF REFRIGERATION, 2008, 31 (08) :1426-1436