Comparison of the response of doubly fed and fixed-speed induction generator wind turbines to changes in network frequency

被引:467
|
作者
Ekanayake, J [1 ]
Jenkins, N
机构
[1] Univ Peradeniya, Peradeniya 20400, Sri Lanka
[2] Univ Manchester, Inst Sci & Technol, MCEE, Manchester M60 1QD, Lancs, England
[3] Tyndall Ctr Climate Change Res, Norwich NR4 7TJ, Norfolk, England
关键词
doubly fed; fixed speed; frequency response; inertia; wind turbines;
D O I
10.1109/TEC.2004.827712
中图分类号
TE [石油、天然气工业]; TK [能源与动力工程];
学科分类号
0807 ; 0820 ;
摘要
Synchronous and fixed-speed induction generators release the kinetic energy of their rotating mass when the power system frequency is reduced. In the case of doubly fed induction generator (DFIG)-based wind turbines, their control system operates to apply a restraining torque to the rotor according to a predetermined curve with respect to the rotor speed. This control system is not based on the power system frequency and there is negligible contribution to the inertia of the power system. A DFIG control system was modified to introduce inertia response to the DFIG wind turbine. Simulations were used to show that with the proposed control system, the DFIG wind turbine can supply considerably greater kinetic energy than a fixed-speed wind turbine.
引用
收藏
页码:800 / 802
页数:3
相关论文
共 50 条
  • [1] Power system frequency response from fixed speed and doubly fed induction generator based wind turbines
    Holdsworth, L
    Ekanayake, JB
    Jenkins, N
    WIND ENERGY, 2004, 7 (01) : 21 - 35
  • [2] Comparison of primary frequency control methods for wind turbines based on the doubly fed induction generator
    Amaro Pinazo, Mauro
    Antara Arias, Ronal
    Mirez Tarrillo, Jorge
    WIND ENGINEERING, 2022, 46 (06) : 1923 - 1947
  • [3] Mechanical stresses in fixed-speed wind turbines due to network disturbances
    Papathanassiou, SA
    Papadopoulos, MP
    IEEE TRANSACTIONS ON ENERGY CONVERSION, 2001, 16 (04) : 361 - 367
  • [4] Estimation of Effective Wind Speed for Fixed-Speed Wind Turbines Based on Frequency Domain Data Fusion
    Xu, Zhiqiang
    Hu, Qinghua
    Ehsani, Mehrdad
    IEEE TRANSACTIONS ON SUSTAINABLE ENERGY, 2012, 3 (01) : 57 - 64
  • [5] Comparison among series compensators for transient stability enhancement of doubly fed induction generator based variable speed wind turbines
    Abu Hussein, Ahmed
    Ali, Mohd. Hasan
    IET RENEWABLE POWER GENERATION, 2016, 10 (01) : 116 - 126
  • [6] A variable droop control strategy for doubly fed induction generator wind turbines
    Pan, Wenxia
    Quan, Rui
    Wang, Fei
    Dianli Xitong Zidonghua/Automation of Electric Power Systems, 2015, 39 (11): : 126 - 131and186
  • [7] Comparison of an aggregated model of a wind farm consisting of fixed-speed wind turbines with field measurement
    Perdana, Abram
    Uski-Joutsenvuo, Sanna
    Carlson, Ola
    Lemstrom, Bettina
    WIND ENERGY, 2008, 11 (01) : 13 - 27
  • [8] Transient Model Validation of Fixed-Speed Induction Generator Using Wind Farm Measurements
    Rogdakis, Georgios
    Garcia-Valle, Rodrigo
    Arana, Ivan
    IEEE TRANSACTIONS ON POWER SYSTEMS, 2012, 27 (01) : 564 - 571
  • [9] Response of Fixed Speed Wind Turbines to System Frequency Disturbances
    Sumper, Andreas
    Gomis-Belimunt, Oriol
    Sudria-Andreu, Antoni
    Villafafila-Robles, Roberto
    Rull-Duran, Joan
    IEEE TRANSACTIONS ON POWER SYSTEMS, 2009, 24 (01) : 181 - 192
  • [10] Fixed-speed active-stall wind turbines in offshore applications
    Akhmatov, V
    Nielsen, AH
    EUROPEAN TRANSACTIONS ON ELECTRICAL POWER, 2005, 15 (01): : 1 - 12