Improved Control of Radiator Heating Systems with Thermostatic Radiator Valves without Pre-Setting Function

被引:22
作者
Benakopoulos, Theofanis [1 ,2 ,3 ]
Salenbien, Robbe [1 ,2 ]
Vanhoudt, Dirk [1 ,2 ]
Svendsen, Svend [3 ]
机构
[1] Vlaamse Instelling Technol Onderzoek VITO NV, Boeretang 200, B-2400 Mol, Belgium
[2] EnergyVille, Thor Pk 8310, B-3600 Genk, Belgium
[3] Tech Univ Denmark, Dept Civil Engn, Bldg 118, DK-2800 Lyngby, Denmark
关键词
low-temperature district heating; radiator heating system; thermostatic radiator valves; low-temperature operation; low supply temperature; multi-family building; thermal-hydraulic model; return temperature measurements; TEMPERATURE;
D O I
10.3390/en12173215
中图分类号
TE [石油、天然气工业]; TK [能源与动力工程];
学科分类号
0807 ; 0820 ;
摘要
Low-temperature district heating will play an important role in a future free of fossil fuels. This will only be able to be realized through the low-temperature operation of heating systems in existing buildings. Existing radiator systems can operate with low temperatures for most of the year because they are designed for extremely cold days, but errors have to be corrected and the control of the radiator systems needs to be improved. In this paper, we present a strategy to achieve low-temperature operation from the radiator system of a multi-family building in Denmark without a pre-setting function in the thermostatic radiator valves. The strategy is based on operating the system with a combination of a minimum supply temperature and small temperature differences over the radiators. The operation of the system is analyzed through a thermal-hydraulic model. A minimum supply temperature weather compensation curve was calculated and implemented in the central supply temperature control. Return temperature measurements in the substation, the risers, and several critical radiators were performed before and after the implementation of the strategy. The measurements confirm that a lower supply temperature results in a reduction of the return temperature. However, the system operator needs to be supported by a tool package to correctly maintain the system's operation.
引用
收藏
页数:24
相关论文
共 29 条
[1]   Investigation of hydraulic imbalance for converting existing boiler based buildings to low temperature district heating [J].
Ashfaq, Asad ;
Ianakiev, Anton .
ENERGY, 2018, 160 :200-212
[2]   The role of thermostatic radiator valves for the control of space heating in UK social-rented households [J].
Bruce-Konuah, Adorkor ;
Jones, Rory, V ;
Fuertes, Alba ;
Messi, Leonardo ;
Giretti, Alberto .
ENERGY AND BUILDINGS, 2018, 173 :206-220
[3]   Heat Roadmap Europe: Combining district heating with heat savings to decarbonise the EU energy system [J].
Connolly, D. ;
Lund, H. ;
Mathiesen, B. V. ;
Werner, S. ;
Moller, B. ;
Persson, U. ;
Boermans, T. ;
Trier, D. ;
Ostergaard, P. A. ;
Nielsen, S. .
ENERGY POLICY, 2014, 65 :475-489
[4]  
Danish Standards, 2005, 14336 DSEN
[5]  
Danish Standards, 2011, 418 DSFDS
[6]  
European Commission, EN EFF HEAT COOL
[7]  
European Commission, 2011, EUR 2020 FLAGSH IN I
[8]  
European Commission, COM (2018) 773 final
[9]   Fault detection in district heating substations [J].
Gadd, Henrik ;
Werner, Sven .
APPLIED ENERGY, 2015, 157 :51-59
[10]   Achieving low return temperatures from district heating substations [J].
Gadd, Henrik ;
Werner, Sven .
APPLIED ENERGY, 2014, 136 :59-67