Methodology to assess distribution transformer thermal capacity for uptake of low carbon technologies

被引:19
作者
Gao, Yuan [1 ]
Patel, Beval [1 ]
Liu, Qiang [1 ]
Wang, Zhongdong [1 ]
Bryson, Geraldine [2 ]
机构
[1] Univ Manchester, Sch Elect & Elect Engn, Manchester M13 9PL, Lancs, England
[2] Elect North West Ltd, 304 Bridgewater Pl,Birchwood Pk, Warrington WA3 6XG, Cheshire, England
关键词
IMPACT;
D O I
10.1049/iet-gtd.2016.0722
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
Low-voltage network is concerned on the penetration of low carbon technologies. Distribution transformer thermal capacity is one of the most concerned, due to the aged and capital-intensive nature of the transformer fleet. Extensive studies have been done on this topic, and most of them have applied exiting thermal models such as IEC 60076 thermal model to estimate the hot-spot temperature (HST). However, it is lack of consideration on how accurate the thermal model is or how to refine the thermal model for more accurate estimation of HST. In this study, a methodology is introduced to improve the accuracy of IEC thermal model by refining its thermal parameters based on measured temperature data during the heat run test. Verification of the methodology under one 1 MVA 6.6/0.415 kV distribution transformer shows that the accuracy of predicting the HST is improved by reducing the maximum error from 25.8 to 3.6 K under constant loads and 8.15 to 4.16 K under cyclic loads. Also, a worst-case scenario study under the penetration of electric vehicles (EVs) shows the maximum penetration level of EVs is improved by 9% by applying refined thermal parameters to estimate the HST of the distribution transformer.
引用
收藏
页码:1645 / 1651
页数:7
相关论文
共 21 条
  • [1] [Anonymous], 2005, 6007672005 BS IEC
  • [2] [Anonymous], 2012, IEEE Std C57.91-2011
  • [3] [Anonymous], 2011, 6007622011 BS EN
  • [4] [Anonymous], 2007, ENV ASS PLUG IN HYBR
  • [5] [BERR DfT], 2008, INV SCOP TRANSP SECT
  • [6] Gao Y., 2014, INT C COND MON DIAGN
  • [7] Gao Y., 2013, EUR TECHCON 2013 GLA
  • [8] PEV Charging Control Considering Transformer Life and Experimental Validation of a 25 kVA Distribution Transformer
    Gong, Qiuming
    Midlam-Mohler, Shawn
    Serra, Emmanuele
    Marano, Vincenzo
    Rizzoni, Giorgio
    [J]. IEEE TRANSACTIONS ON SMART GRID, 2015, 6 (02) : 648 - 656
  • [9] Heathcote M., 2007, J P TRANSFORMER BOOK
  • [10] Estimating the Impact of Electric Vehicle Smart Charging on Distribution Transformer Aging
    Hilshey, Alexander D.
    Hines, Paul D. H.
    Rezaei, Pooya
    Dowds, Jonathan R.
    [J]. IEEE TRANSACTIONS ON SMART GRID, 2013, 4 (02) : 905 - 913