A New Fault-Location Algorithm for Extra-High-Voltage Mixed Lines Based on Phase Characteristics of the Hyperbolic Tangent Function

被引:31
作者
Zhang, Shuai [1 ]
Gao, Houlei [1 ]
Song, Yingtao [1 ]
机构
[1] Shandong Univ, Minist Educ, Key Lab Power Syst Intelligent Dispatch & Control, Jinan 250061, Peoples R China
基金
中国国家自然科学基金;
关键词
Fault location; faulted section identification; hyperbolic tangent; mixed lines; phase characteristics; CLOSED-FORM SOLUTION; TRANSMISSION-LINES; DETECTION/LOCATION TECHNIQUE; SCHEME; RELAY;
D O I
10.1109/TPWRD.2015.2461678
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
A new fault-location algorithm for extra-high-voltage mixed lines based on phase characteristics of the hyperbolic tangent function is proposed. This paper takes overhead-cable-overhead mixed lines for example. The faulted section identification functions for overhead cable connections described by the hyperbolic tangent are developed separately when faults occur on the first overhead line, the middle cable, and the last overhead line. When a fault occurs on different sections, the faulted section identification functions appear as obviously different phase characteristics according to the phase characteristics of the hyperbolic tangent function. Thus, the faulted section can be identified. The fault location can be therefore accurately determined with the voltage and current positive-sequence fault components on both ends of the faulted section. Simulations and calculations with PSCAD and MATALB show that the fault-location algorithm is correct and accurate.
引用
收藏
页码:1203 / 1212
页数:10
相关论文
共 36 条
[1]  
[Anonymous], 2007, P 2007 IEEE POW ENG, DOI DOI 10.1109/PES.2007.385545
[2]   A Novel Algorithm for Locating Faults on Transposed/Untransposed Transmission Lines Without Utilizing Line Parameters [J].
Apostolopoulos, Christos A. ;
Korres, George N. .
IEEE TRANSACTIONS ON POWER DELIVERY, 2010, 25 (04) :2328-2338
[3]   Cross-bonding cable and box model based on pulse reflection measurement [J].
de Regt, Jos J. ;
Hoogendorp, Gerben ;
Wagenaars, Paul ;
Wouters, Peter A. A. F. ;
Popov, Marjan ;
van der Sluis, Lou ;
Steennis, E. Fred .
IET SCIENCE MEASUREMENT & TECHNOLOGY, 2015, 9 (03) :268-275
[4]  
El Din EST, 2006, ELECTR POW SYST RES, V76, P928, DOI [10.1016/j.epsr.2005.07.008, 10.1016/j.epsr.2005.07.005]
[5]  
Fuhong L., 2011, ELECT POWER AUTOM EQ, V31, P82
[6]   Traveling-wave-based fault-location scheme for multiend-aged underground cable system [J].
Gilany, Mahmoud ;
Ibrahim, Doaa Khalil ;
Eldin, El Sayed Tag .
IEEE TRANSACTIONS ON POWER DELIVERY, 2007, 22 (01) :82-89
[7]   Field Test and Simulation of a 400-kV Cross-Bonded Cable System [J].
Gudmundsdottir, Unnur Stella ;
Gustavsen, Bjorn ;
Bak, Claus Leth ;
Wiechowski, Wojciech .
IEEE TRANSACTIONS ON POWER DELIVERY, 2011, 26 (03) :1403-1410
[8]  
Han J., 2014, 12th IET International Conference on Developments in Power System Protection (DPSP 2014), Copenhagen, P1
[9]  
Han JM, 2013, PROCEEDINGS OF 2013 CHINA INTERNATIONAL CONFERENCE ON INSURANCE AND RISK MANAGEMENT, P1
[10]  
Jiang JA, 2000, IEEE T POWER DELIVER, V15, P486