Exergy Analysis: a Three-heat-source (Air, Wastewater & Energy Recycle) Hot Water System

被引:0
|
作者
Zhang, Zhongbin [1 ]
Huang, Hu [1 ]
Yang, Dongdong
Yu, Jia [1 ]
Chen, Zemin
机构
[1] Nanjing Normal Univ, Sch Dynam Engn, Nanjing, Peoples R China
来源
6TH INTERNATIONAL SYMPOSIUM ON HEATING, VENTILATING AND AIR CONDITIONING, VOLS I-III, PROCEEDINGS | 2009年
关键词
Three-heat-source hot-water system; Exergy analysis; Thermal calculation; energy-saving; HEAT-PUMP SYSTEMS;
D O I
暂无
中图分类号
O414.1 [热力学];
学科分类号
摘要
In this paper, comparison on air-source heat pump hot water system (ASHP), groundwater source heat pump hot water system (GSHP) and three-heat-source hot-water system (TSHS) were analyzed. The TSHS operates with ASHP running with valley electricity during night, waste heat of bath recycled during afternoon, and wastewater-source heat pump hot water system (WSHP) running with peak electricity. Based on the meteorological parameter condition in Nanjing, environmental temperatures for ASHP were chosen as 35 degrees C, 20 degrees C, 7 degrees C and -6 degrees C respectively, for GSHP, 18 degrees C, for WSHP, 30 degrees C. Other data for these three systems are made the same: fresh water for bath at 45 degrees C, condensing temperature t(k)=58 degrees C, evaporating temperature to be confirmed according to environmental temperature, superheat degree SH-10 degrees C, super cooling degree SC-5 degrees C, isentropic efficiency of compressor eta(i)=0.75. Based on the above condition, thermodynamic calculation and exergy analysis were made on these three systems. Results indicate that: work condition of ASHP varies considerably, while those of GSHP and WSHP are steady on the whole. Annual average exergy efficiency of ASHP (13.82%), which increases accordingly with the increase of high temperature runtime (17.92% maximum), is the weighted average of exergy efficiencies in four environments. The annual average exergy efficiency of GSHP is 15.36% and that of WSHP is 23.97%. The annual average exergy efficiency of TSHS, determined by the rate of the runtime of ASHP and WSHP, which should be calculated with the cost of valley and peak electricity considered, varies between 13.82% and 23.97%. As is shown in the conclusion, TSHS is well worth popularization for it runs at a steady course with low cost and high efficiency, especially for schools which do not need hot water system during the time at the highest and lowest temperature.
引用
收藏
页码:1514 / 1520
页数:7
相关论文
共 50 条
  • [21] Steady versus dynamic exergy analysis: the case of an air source heat pump
    Angelotti, Adriana
    Caputo, Paola
    Solaini, Giulio
    INTERNATIONAL JOURNAL OF EXERGY, 2012, 11 (04) : 460 - 472
  • [22] EXERGY ANALYSIS OF A RADIANT CEILING ASSISTED GROUND-SOURCE HEAT PUMP AIR-CONDITIONING SYSTEM
    Sui, Xuemin
    Zhang, Xu
    Lin, Ting
    FIFTH INTERNATIONAL WORKSHOP ON ENERGY AND ENVIRONMENT OF RESIDENTIAL BUILDINGS AND THIRD INTERNATIONAL CONFERENCE ON BUILT ENVIRONMENT AND PUBLIC HEALTH, VOL I AND II, PROCEEDINGS, 2009, : 1844 - 1851
  • [23] Exergy Analysis of Energy Consumption for Central Air Conditioning System
    Xia, Xiaoxia
    Zhou, Naijun
    Wang, Zhiqi
    MATERIALS SCIENCE, MECHANICAL ENGINEERING AND APPLIED RESEARCH, 2014, 628 : 332 - 337
  • [24] Energy, Exergy analysis and optimization of solar thermal power plant with adding heat and water recovery system
    Vakilabadi, M. Akbari
    Bidi, M.
    Najafi, A. F.
    ENERGY CONVERSION AND MANAGEMENT, 2018, 171 : 1639 - 1650
  • [25] Exergy Analysis of Energy Consumption for Primary Return Air Conditioning System
    Xia Xiao-xia
    Wang Zhi-qi
    Xu Shun-sheng
    2010 INTERNATIONAL CONFERENCE ON COMMUNICATION AND VEHICULAR TECHNOLOGY (ICCVT 2010), VOL II, 2010, : 476 - 479
  • [26] Exergy Analysis of Energy Consumption for Primary Return Air Conditioning System
    Xia Xiao-xia
    Wang Zhi-qi
    Xu Shun-sheng
    INTERNATIONAL CONFERENCE ON APPLIED PHYSICS AND INDUSTRIAL ENGINEERING 2012, PT C, 2012, 24 : 2131 - 2137
  • [27] Experimental study on a novel PV/T air dual-heat-source composite heat pump hot water system
    Wang, Gang
    Quan, Zhenhua
    Zhao, Yaohua
    Sun, Chenming
    Deng, Yuechao
    Tong, Jiannan
    ENERGY AND BUILDINGS, 2015, 108 : 175 - 184
  • [28] Application of Exergy Analysis to Chilled Water Circuit and Heat Pump System
    Yin, Hang
    Ooka, Ryozo
    Shukuya, Masanori
    6TH INTERNATIONAL BUILDING PHYSICS CONFERENCE (IBPC 2015), 2015, 78 : 1075 - 1080
  • [29] Exergy and exergoeconomic analysis of a Compressed Air Energy Storage combined with a district energy system
    Bagdanavicius, Audrius
    Jenkins, Nick
    ENERGY CONVERSION AND MANAGEMENT, 2014, 77 : 432 - 440
  • [30] Energy and exergy analysis of a novel pumped hydro compressed air energy storage system
    Yang, Biao
    Li, Deyou
    Fu, Xiaolong
    Wang, Hongjie
    Gong, Ruzhi