Exergy Analysis: a Three-heat-source (Air, Wastewater & Energy Recycle) Hot Water System

被引:0
|
作者
Zhang, Zhongbin [1 ]
Huang, Hu [1 ]
Yang, Dongdong
Yu, Jia [1 ]
Chen, Zemin
机构
[1] Nanjing Normal Univ, Sch Dynam Engn, Nanjing, Peoples R China
来源
6TH INTERNATIONAL SYMPOSIUM ON HEATING, VENTILATING AND AIR CONDITIONING, VOLS I-III, PROCEEDINGS | 2009年
关键词
Three-heat-source hot-water system; Exergy analysis; Thermal calculation; energy-saving; HEAT-PUMP SYSTEMS;
D O I
暂无
中图分类号
O414.1 [热力学];
学科分类号
摘要
In this paper, comparison on air-source heat pump hot water system (ASHP), groundwater source heat pump hot water system (GSHP) and three-heat-source hot-water system (TSHS) were analyzed. The TSHS operates with ASHP running with valley electricity during night, waste heat of bath recycled during afternoon, and wastewater-source heat pump hot water system (WSHP) running with peak electricity. Based on the meteorological parameter condition in Nanjing, environmental temperatures for ASHP were chosen as 35 degrees C, 20 degrees C, 7 degrees C and -6 degrees C respectively, for GSHP, 18 degrees C, for WSHP, 30 degrees C. Other data for these three systems are made the same: fresh water for bath at 45 degrees C, condensing temperature t(k)=58 degrees C, evaporating temperature to be confirmed according to environmental temperature, superheat degree SH-10 degrees C, super cooling degree SC-5 degrees C, isentropic efficiency of compressor eta(i)=0.75. Based on the above condition, thermodynamic calculation and exergy analysis were made on these three systems. Results indicate that: work condition of ASHP varies considerably, while those of GSHP and WSHP are steady on the whole. Annual average exergy efficiency of ASHP (13.82%), which increases accordingly with the increase of high temperature runtime (17.92% maximum), is the weighted average of exergy efficiencies in four environments. The annual average exergy efficiency of GSHP is 15.36% and that of WSHP is 23.97%. The annual average exergy efficiency of TSHS, determined by the rate of the runtime of ASHP and WSHP, which should be calculated with the cost of valley and peak electricity considered, varies between 13.82% and 23.97%. As is shown in the conclusion, TSHS is well worth popularization for it runs at a steady course with low cost and high efficiency, especially for schools which do not need hot water system during the time at the highest and lowest temperature.
引用
收藏
页码:1514 / 1520
页数:7
相关论文
共 50 条
  • [1] Experimental study of air source heat pump water heater: Energy, exergy, and entransy analysis
    Ruan F.
    Xu S.
    Qin D.
    Li S.
    Chen P.
    Ruan, Fang (rufa2002@163.com), 2025, 6 (02): : 187 - 200
  • [2] Exergy and Energy Analysis of Coal Gasification in Supercritical Water with External Recycle System
    Wang, Cui
    Jin, Hui
    Fan, Chao
    Luo, Kui
    Guo, Shenghui
    INTERNATIONAL JOURNAL OF CHEMICAL REACTOR ENGINEERING, 2019, 17 (11)
  • [3] Exergy analysis of mine water source heat pump system
    Wang Jinggang
    Du Meixia
    Du Chuanchuan
    Gao Xiaoxia
    NANOTECHNOLOGY AND COMPUTER ENGINEERING, 2010, 121-122 : 980 - +
  • [4] Energy and Exergy Analysis of a Ground Water Heat Pump System
    Lei Fei
    Hu Pingfang
    INTERNATIONAL CONFERENCE ON APPLIED PHYSICS AND INDUSTRIAL ENGINEERING 2012, PT A, 2012, 24 : 169 - 175
  • [5] Energy and exergy analysis of a geothermal energy sourced hot-air drying system
    Helvaci, Huseyin Utku
    Keles, Nazli
    Akkurt, Gulden Gokcen
    INTERNATIONAL JOURNAL OF EXERGY, 2023, 41 (01) : 1 - 19
  • [6] Energy and exergy analysis of a ground source (geothermal) heat pump system
    Hepbasli, A
    Akdemir, O
    ENERGY CONVERSION AND MANAGEMENT, 2004, 45 (05) : 737 - 753
  • [7] Energy and exergy analysis of a geothermal heat pump air conditioning system
    Baccoli, Roberto
    Mastino, Costantino
    Rodriguez, Giuseppe
    APPLIED THERMAL ENGINEERING, 2015, 86 : 333 - 347
  • [8] Energy and exergy analysis of solar integrated air source heat pump for radiant floor heating without water
    Dong, Xu
    Tian, Qi
    Li, Zhen
    ENERGY AND BUILDINGS, 2017, 142 : 128 - 138
  • [9] Comparison of energy and exergy analysis of fossil plant, ground and air source heat pump building heating system
    Lohani, S. P.
    Schmidt, D.
    RENEWABLE ENERGY, 2010, 35 (06) : 1275 - 1282
  • [10] Energy, exergy, economic and environmental analysis of refrigerant charge in air source transcritical carbon dioxide heat pump water heater
    Wang, Yikai
    Ye, Zuliang
    Song, Yulong
    Yin, Xiang
    Cao, Feng
    ENERGY CONVERSION AND MANAGEMENT, 2020, 223