A fast distance relay using adaptive data window filters

被引:0
作者
Sidhu, TS [1 ]
Ghotra, DS [1 ]
Sachdev, MS [1 ]
机构
[1] Univ Saskatchewan, Power Syst Res Grp, Saskatoon, SK S7N 5A9, Canada
来源
2000 IEEE POWER ENGINEERING SOCIETY SUMMER MEETING, CONFERENCE PROCEEDINGS, VOLS 1-4 | 2000年
关键词
transmission line protection; distance relay; adaptive data window filters;
D O I
暂无
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
This paper describes the design of a distance relay that uses adaptive data window filters to provide high speed tripping. The relay uses a fault detector to detect the inception of a fault. Starting from the fault detection, the data window size is progressively increased as new fault samples become available until the window size becomes one cycle of the fundamental frequency. At each instant, a suitable filter is used for estimating voltage and current phasors. This procedure improves the transient response of the relay and allows faster convergence of the impedance estimates and, therefore, reduces the trip time. The proposed relay was tested by using fault simulations on a sample power system Results indicate that the proposed relay design reduces the trip times.
引用
收藏
页码:1407 / 1412
页数:4
相关论文
共 7 条
  • [1] HIGH-SPEED DISTANCE RELAYING USING A DIGITAL-COMPUTER .1. SYSTEM DESCRIPTION
    GILCREST, GB
    UDREN, EA
    ROCKEFELLER, GD
    [J]. IEEE TRANSACTIONS ON POWER APPARATUS AND SYSTEMS, 1972, PA91 (03): : 1235 - +
  • [2] DIGITAL CALCULATION OF IMPEDANCE FOR TRANSMISSION LINE PROTECTION
    MANN, BJ
    MORRISON, IF
    [J]. IEEE TRANSACTIONS ON POWER APPARATUS AND SYSTEMS, 1971, PA90 (01): : 270 - &
  • [3] Phadke A.G., 2009, Computer Relaying For Power Systems
  • [4] Sachdev M. S., 1997, IEEE TUTORIAL COURSE
  • [5] NEW ALGORITHM FOR DIGITAL IMPEDANCE RELAYS
    SACHDEV, MS
    BARIBEAU, MA
    [J]. IEEE TRANSACTIONS ON POWER APPARATUS AND SYSTEMS, 1979, 98 (06): : 2232 - 2240
  • [6] SACHDEV MS, 1979, IEEE PUBLICATION, V79
  • [7] SACHDEV MS, 1988, IEEE TUTORIAL COURSE