Effects of connection conditions between insulation screen and Al sheath on the buffer layer failures of high-voltage XLPE cables

被引:35
作者
Chen, Yun [1 ]
Hui, Baojun [1 ,2 ]
Cheng, Yanting [1 ]
Chen, Yanwen [1 ]
Hao, Yanpeng [1 ]
Fu, Mingli [2 ]
Yang, Lin [1 ]
Li, Licheng [1 ]
机构
[1] South China Univ Technol, Sch Elect Power Engn, Guangzhou 510641, Peoples R China
[2] China Southern Power Grid, Elect Power Res Inst, Guangzhou 510080, Peoples R China
基金
中国国家自然科学基金;
关键词
Ablation; Buffer layer; Connection condition; High-voltage XLPE cables; Partial discharge; Potential difference; PARTIAL DISCHARGE;
D O I
10.1016/j.engfailanal.2021.105263
中图分类号
TH [机械、仪表工业];
学科分类号
0802 ;
摘要
Recently, high-voltage XLPE cables often suffer from buffer layer failures. The typical characteristics are white powder and ablation appear on the insulation screens, buffer layers, and corrugated aluminum (Al) sheaths. However, little is known about the causes of failure. In this paper, two test platforms of material samples and a cable sample were set up. Partial discharge tests were carried out with material samples, a cable sample, and buffer layer simulation samples to study the resistance and discharge characteristics under different connection conditions between the insulation screen and corrugated Al sheath (IS-Al). The buffer layer?s ablation was reproduced in the material samples test. The material samples test revealed that partial discharge was easy to occur when IS-Al?s air gaps were tiny, or the IS-Al was ?point connection? without air gaps. The buffer layer simulation samples test indicated that the better the IS-Al?s connection conditions are, the smaller the resistance, potential difference, and discharge quantity are, and the more stable the discharge pulse is. Judging from these results, the IS-Al?s connection conditions seem to impact the buffer layer failures of high-voltage XLPE cables.
引用
收藏
页数:9
相关论文
共 16 条
[1]   Detection and Localization of Defects in Cable Sheath of Cross-Bonding Configuration by Sheath Currents [J].
Adel Shokry, Marina ;
Khamlichi, Abderrahim ;
Garnacho, Fernando ;
Malo, Julio Martinez ;
Alvarez, Fernando .
IEEE TRANSACTIONS ON POWER DELIVERY, 2019, 34 (04) :1401-1411
[2]  
[Anonymous], 2015, CS915 AEIC
[3]  
[Anonymous], 2019, 1234TM IEEE
[4]  
[Anonymous], 2015, 608853 IEC
[5]   Theoretical Basis of "Track" Morphology in the Growth Region of a Water Tree [J].
Boggs, Steven ;
Shu, Wen .
IEEE TRANSACTIONS ON DIELECTRICS AND ELECTRICAL INSULATION, 2019, 26 (01) :235-239
[6]   Modeling Partial Discharge in a Three-phase Cable Joint Experiment with Minimal Adjustable Parameters [J].
Callender, G. ;
Lewin, P. L. ;
Hunter, J. A. ;
Rapisarda, P. .
IEEE TRANSACTIONS ON DIELECTRICS AND ELECTRICAL INSULATION, 2017, 24 (01) :279-287
[7]   Failure investigation of buffer layers in high-voltage XLPE cables [J].
Chen, Yun ;
Hui, Baojun ;
Cheng, Yanting ;
Hao, Yanpeng ;
Fu, Mingli ;
Yang, Lin ;
Hou, Shuai ;
Li, Licheng .
ENGINEERING FAILURE ANALYSIS, 2020, 113
[8]   Ageing mechanisms and diagnostics for power cables - An overview [J].
Densley, J .
IEEE ELECTRICAL INSULATION MAGAZINE, 2001, 17 (01) :14-22
[9]   Generation of acoustic phase-resolved partial discharge patterns by utilizing UHF signals [J].
Ilkhechi, Hossein Dadashi ;
Samimi, Mohammad Hamed ;
Yousefvand, Reza .
INTERNATIONAL JOURNAL OF ELECTRICAL POWER & ENERGY SYSTEMS, 2019, 113 :906-915
[10]  
Jiang L, 2019, 2019 2ND INTERNATIONAL CONFERENCE ON ELECTRICAL MATERIALS AND POWER EQUIPMENT (ICEMPE 2019), P372, DOI [10.1109/ICEMPE.2019.8727342, 10.1109/icempe.2019.8727342]