Exergetic analysis of a double stage LiBr-H2O thermal compressor cooled by air/water and driven by low grade heat

被引:26
作者
Izquierdo, M
Venegas, M
García, N
Palacios, E
机构
[1] CSIC, InstCC Eduardo Torroja, Madrid 28033, Spain
[2] Univ Carlos 3 Madrid, Dept Ingn Term & Fluidos, Madrid 28911, Spain
[3] Univ Politecn Madrid, EUITI, Dept Mecan Ind, Madrid 28012, Spain
关键词
double stage thermal compressor; low-grade heat; entropy generated; exergy destroyed; exergetic efficiency;
D O I
10.1016/j.enconman.2004.06.016
中图分类号
O414.1 [热力学];
学科分类号
摘要
In the present paper, an exergetic analysis of a double stage thermal compressor using the lithium bromide-water solution is performed. The double stage system considered allows obtaining evaporation temperatures equal to 5 degreesC using solar heat coming from flat plate collectors and other low grade thermal sources. In this study, ambient air and water are alternatively used as cooling fluids without crystallization problems up to condensation-absorption temperatures equal to 50 degreesC. The results obtained give the entropy generated, the exergy destroyed and the exergetic efficiency of the double stage thermal compressor as a function of the absorption temperature. The conclusions obtained show that the irreversibilities generated by the double stage thermal compressor will tend to increase with the absorption temperature up to 45 degreesC. The maximum value corresponds to 1.35 kJ kg(-1) K-1. The entropy generated and the exergy destroyed by the air cooled system are higher than those by the water cooled one. The difference between the values increases when the absorption temperature increases. For an absorption temperature, equal to 50 degreesC, the air cooled mode generates 14% more entropy and destroys 149/6 more exergy than the water cooled one. Also, the results are compared with those of previous studies for single and double effect air cooled and water cooled thermal compressors. The conclusions show that the double stage system has about 22% less exergetic efficiency than the single effect one and 32% less exergetic efficiency than the double effect one. (C) 2004 Elsevier Ltd. All rights reserved.
引用
收藏
页码:1029 / 1042
页数:14
相关论文
共 18 条
  • [1] Second law based thermodynamic analysis of ammonia-water absorption systems
    Adewusi, SA
    Zubair, SM
    [J]. ENERGY CONVERSION AND MANAGEMENT, 2004, 45 (15-16) : 2355 - 2369
  • [2] Arzoz D, 2002, PROCEEDINGS OF THE INTERNATIONAL SORPTION HEAT PUMP CONFERENCE, P101
  • [3] Bejan Adrian., 1995, THERMAL DESIGN OPTIM
  • [4] Thermodynamic analysis of the main devices for thermal energy upgrading
    Bisio, G
    [J]. ENERGY CONVERSION AND MANAGEMENT, 1998, 39 (3-4) : 229 - 242
  • [5] Entropy production analysis and experimental confirmation of absorption systems
    Chua, HT
    Gordon, JM
    Ng, KC
    Han, Q
    [J]. INTERNATIONAL JOURNAL OF REFRIGERATION-REVUE INTERNATIONALE DU FROID, 1997, 20 (03): : 179 - 190
  • [6] THE NATURAL GAS-ABSORPTION METHOD SYSTEM AS AN ALTERNATIVE TO THE ELECTRIC POWER-MECHANICAL COMPRESSION SYSTEM IN SPAIN
    HERNANDEZ, F
    IZQUIERDO, M
    [J]. ENERGY CONVERSION AND MANAGEMENT, 1993, 34 (08) : 663 - 676
  • [7] Crystallization as a limit to develop solar air-cooled LiBr-H2O absorption systems using low-grade heat
    Izquierdo, M
    Venegas, M
    Rodríguez, P
    Lecuona, A
    [J]. SOLAR ENERGY MATERIALS AND SOLAR CELLS, 2004, 81 (02) : 205 - 216
  • [8] Compressors driven by thermal solar energy:: entropy generated, exergy destroyed and exergetic efficiency
    Izquierdo, M
    De Vega, M
    Lecuona, A
    Rodríguez, P
    [J]. SOLAR ENERGY, 2002, 72 (04) : 363 - 375
  • [9] Kim DS, 2002, PROCEEDINGS OF THE INTERNATIONAL SORPTION HEAT PUMP CONFERENCE, P117
  • [10] Opportunities for sorption cooling using low grade heat
    Lamp, P
    Schweigler, C
    Ziegler, F
    [J]. APPLIED THERMAL ENGINEERING, 1998, 18 (9-10) : 755 - 764