An epistemic indoor air quality assessment protocol for air-conditioned offices

被引:15
作者
Hui, P. S. [1 ]
Wong, L. T. [1 ]
Mui, K. W. [1 ]
机构
[1] Hong Kong Polytech Univ, Dept Bldg Serv Engn, Kowloon, Hong Kong, Peoples R China
关键词
IAQ; epistemic assessment; CO2; measurements; air-conditioned offices;
D O I
10.1177/1420326X07076503
中图分类号
TU [建筑科学];
学科分类号
0813 ;
摘要
Long-term measurement could be the best approach to determine the average pollutant concentration of an indoor environment for decisions on mitigation measures. This approach requires considerable measurement effort for accurate results and hence indoor air quality (IAQ) assessment methods that need less effort have been cleveloped.This study proposes an epistemic approach for assessing an acceptable office IAQ against certain indoor air pollutant exposure limits. Together with the prior understanding of failure rates of IAQ determined from a number of extensive survey studies, a sample test result of pollutant levels and the uncertainties of different sampling schemes, the probability of satisfactory IAQ for an assessed air-conditioned office could be quantified. In particular, assessment of an acceptable IAQ for some air-conditioned offices in Hong Kong was demonstrated by taking CO2 as an example pollutant. Accuracy of the failure rates was improved by the application of sampling correction factors and Bayesian statistics. The probabilities of an acceptable office IAQ were evaluated against a CO2 level limit. This approach would be useful for IAQ assessment in some air-conditioned offices.
引用
收藏
页码:139 / 147
页数:9
相关论文
共 38 条
[1]  
*AM SOC HEAT REFR, 1989, 621989 ANSIASHRAE
[2]   Numerical modelling of radon-222 entry into houses: an outline of techniques and results [J].
Andersen, CE .
SCIENCE OF THE TOTAL ENVIRONMENT, 2001, 272 (1-3) :33-42
[3]  
[Anonymous], APPL OCCUP ENV HYG
[4]  
[Anonymous], EXP GUID RES IND AIR
[5]  
[Anonymous], STAT KNOWL REP AIR T
[6]  
ARMSTRONG BK, 1992, EXPOSURE MEASUREMENT
[7]  
*CEN, 1998, CR1752 CEN ENV I DIR
[8]  
CRANDALL MS, 1996, APPL OCCUP ENV HYG, V11, P533
[9]  
ENV Ministry of the Environment, 1996, SING GUID GOOD IND A
[10]   THE STANDARD ERROR OF A WEIGHTED MEAN CONCENTRATION .2. ESTIMATING CONFIDENCE-INTERVALS [J].
GATZ, DF ;
SMITH, L .
ATMOSPHERIC ENVIRONMENT, 1995, 29 (11) :1195-1200