Fault control and line protection strategy for LVDC microgrids based on modified high-frequency-link DC solid state transformer

被引:10
作者
Wang, Ting [1 ]
Chu, Xu [1 ]
Hussain, Kazmi Sayed Tassawar [2 ]
Gao, Jiaqi [1 ]
机构
[1] Hunan Univ, Coll Elect & Informat Engn, Lushan Rd, Changsha, Hunan, Peoples R China
[2] Natl Univ Sci & Technol, Islamabad, Pakistan
关键词
Coordination of control and protection; High-frequency-link DC solid state transformer; LVDC microgrid; Line protection; Mechanical circuit breaker;
D O I
10.1016/j.ijepes.2022.108052
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
Fault current with high amplitude and rate of change, together with the vulnerability of electronic devices, poses a great challenge to the line protection in low voltage DC (LVDC) microgrids. A fast fault control and protection method are proposed for LVDC microgrids, based on the modified topology of the high-frequency-link DC solid state transformer (DCSST). By installing two bidirectional antiparallel thyristors in the DCSST and isolation devices at the interface converter side, the freewheeling diodes are protected and current zero-crossings occur due to the submodule capacitor discharge during the fault. Then the line protection could be realized by improved current differential protection, and the mechanical circuit breaker can be tripped around current zero-crossings. It alleviates the high requirement for fast tripping devices (such as solid-state circuit breakers) and fault identification within several milliseconds. The scheme combines the converter fault control with line protection to ensure slow but more economic and reliable fault identification for LVDC grid protection. The proposed strategy is verified by PSCAD/EMTDC simulations and the results show that the fault-tripping-recovery process only takes few tens of milliseconds.
引用
收藏
页数:13
相关论文
共 27 条
  • [1] [Anonymous], DACPOLEUENDIODY ABBP
  • [2] [Anonymous], 2014, 2014 IEEE PES AS PAC
  • [3] Overcurrent protection on voltage-source-converter-based multiterminal DC distribution systems
    Baran, Mesut E.
    Mahajan, Nikhil R.
    [J]. IEEE TRANSACTIONS ON POWER DELIVERY, 2007, 22 (01) : 406 - 412
  • [4] Candeletti F, 2018, INT C HARMON QUAL PO
  • [5] Application and Design of a Resistive-Type Superconducting Fault Current Limiter for Efficient Protection of a DC Microgrid
    Chen, Lei
    Zhang, Xuyang
    Qin, Yuejin
    Chen, Hongkun
    Shen, Qing
    Xu, Ying
    Ren, Li
    Tang, Yuejin
    [J]. IEEE TRANSACTIONS ON APPLIED SUPERCONDUCTIVITY, 2019, 29 (02)
  • [6] An Advanced Protection Scheme for Enabling an LVDC Last Mile Distribution Network
    Emhemed, Abdullah A. S.
    Burt, Graeme M.
    [J]. IEEE TRANSACTIONS ON SMART GRID, 2014, 5 (05) : 2602 - 2609
  • [7] High-Frequency Transformer Isolated Bidirectional DC-DC Converter Modules With High Efficiency Over Wide Load Range for 20 kVA Solid-State Transformer
    Fan, Haifeng
    Li, Hui
    [J]. IEEE TRANSACTIONS ON POWER ELECTRONICS, 2011, 26 (12) : 3599 - 3608
  • [8] Feng X., 2016, 13th International Conference on Development in Power System Protection 2016 (DPSP), P1
  • [9] High-Speed Differential Protection for Smart DC Distribution Systems
    Fletcher, Steven D. A.
    Norman, Patrick J.
    Fong, Kenny
    Galloway, Stuart J.
    Burt, Graeme M.
    [J]. IEEE TRANSACTIONS ON SMART GRID, 2014, 5 (05) : 2610 - 2617
  • [10] DC Transmission Grid With Low-Speed Protection Using Mechanical DC Circuit Breakers
    Hajian, Masood
    Zhang, Lu
    Jovcic, Dragan
    [J]. IEEE TRANSACTIONS ON POWER DELIVERY, 2015, 30 (03) : 1383 - 1391