A reliability-based optimal μ-PMU placement scheme for efficient observability enhancement of smart distribution grids under various contingencies

被引:12
作者
Abdolahi, Arya [1 ]
Taghizadegan, Navid [1 ]
Banaei, Mohamad Reza [1 ]
Salehi, Javad [1 ]
机构
[1] Azarbaijan Shahid Madani Univ, Dept Elect Engn, Tabriz, Iran
关键词
PHASOR MEASUREMENT UNIT; STATE ESTIMATION; DISTRIBUTION NETWORKS; DISTRIBUTION-SYSTEM; GENERATION;
D O I
10.1049/smt2.12067
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
A reliability-based optimal mu-PMU (micro-phasor measurement unit) placement scheme is suggested for efficient observability enhancement of smart distribution grids at steady-state and contingencies conditions. This article introduces a unique method for the mu-PMU allocation in reconfigurable smart distribution grids in which communication system requirements and zero injection nodes (ZINs) are considered. The original objective function and limitations are proposed aiming at minimizing the capital cost, including communication links and installation costs of mu-PMU, optical power ground wire cost, power losses cost, and reliability cost as well as obtaining the maximum number of measurement redundancy constrained to full system observability in the presence of ZINs and tie switches. The suggested method is formulated as a mixed-integer linear programming problem applied to find optimal mu-PMU locations considering the cost of communication infrastructure and co-optimize the system switching plan simultaneously. In this regard, CPLEX-a high-performance mathematical solver-is used to solve the proposed mixed-integer linear optimization problem to reach the global optimality. The simulations are performed on 33, 69, and 85-bus radial distribution networks, and comprehensive simulation studies show the effectiveness of the suggested method.
引用
收藏
页码:663 / 680
页数:18
相关论文
共 47 条
[1]   A novel approach based on crow search algorithm for optimal selection of conductor size in radial distribution networks [J].
Abdelaziz, Almoataz Y. ;
Fathy, Ahmed .
ENGINEERING SCIENCE AND TECHNOLOGY-AN INTERNATIONAL JOURNAL-JESTECH, 2017, 20 (02) :391-402
[2]  
Abdelsalam HA, 2014, CLEM UNIV POWER SYST
[3]   Assessing the potential of merchant energy storage to maximize social welfare of renewable-based distribution networks considering risk analysis [J].
Abdolahi, Arya ;
Salehi, Javad ;
Gazijahani, Farhad Samadi ;
Safari, Amin .
ELECTRIC POWER SYSTEMS RESEARCH, 2020, 188
[4]   Optimal PMU placement for modeling power grid observability with mathematical programming methods [J].
Almunif, Anas ;
Fan, Lingling .
INTERNATIONAL TRANSACTIONS ON ELECTRICAL ENERGY SYSTEMS, 2020, 30 (02)
[5]  
Biswas R. S., 2020, IEEE POW ENER SOC GE, P1, DOI DOI 10.1109/pesgm41954.2020.9282049
[6]   Placement of Synchronized Measurements for Power System Observability [J].
Chakrabarti, Saikat ;
Kyriakides, Elias ;
Eliades, Demetrios G. .
IEEE TRANSACTIONS ON POWER DELIVERY, 2009, 24 (01) :12-19
[7]  
Chaudhary S., 2019, 2019 4 INT C INT THI, P1
[8]   Placement of Distribution-Level Phasor Measurements for Topological Observability and Monitoring of Active Distribution Networks [J].
Chauhan, Kapil ;
Sodhi, Ranjana .
IEEE TRANSACTIONS ON INSTRUMENTATION AND MEASUREMENT, 2020, 69 (06) :3451-3460
[9]   Optimal Meter Placement for Distribution Network State Estimation: A Circuit Representation Based MILP Approach [J].
Chen, Xiaoshuang ;
Lin, Jin ;
Wan, Can ;
Song, Yonghua ;
You, Shi ;
Zong, Yi ;
Guo, Wanfang ;
Li, Yuanxi .
IEEE TRANSACTIONS ON POWER SYSTEMS, 2016, 31 (06) :4357-4370
[10]   Full Coverage of Optimal Phasor Measurement Unit Placement Solutions in Distribution Systems Using Integer Linear Programming [J].
Chen, Xuebing ;
Sun, Lu ;
Chen, Tengpeng ;
Sun, Yuhao ;
Rusli ;
Tseng, King Jet ;
Ling, Keck Voon ;
Ho, Weng Khuen ;
Amaratunga, Gehan A. J. .
ENERGIES, 2019, 12 (08)