Noniterative Parameter-Free Fault Location on Untransposed Single-Circuit Transmission Lines

被引:27
作者
Dobakhshari, Ahmad Salehi [1 ]
机构
[1] Univ Guilan, Fac Engn, Dept Elect Engn, Rasht 4199613776, Iran
关键词
Bisymmetric matrix; fault location; impedance matrix; synchronized measurements; untransposed transmission line; ALGORITHM;
D O I
10.1109/TPWRD.2017.2650780
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
Extra high voltage transmission networks include many untransposed single-circuit overhead lines with horizontal configuration of phase conductors. This paper develops a setting-free fault-location method specific to these types of transmission lines. Utilizing synchronized measurements at line terminals, the proposed method accurately locates faults irrespective of fault type, fault resistance, external network parameters, and faulted-line parameters. As such, fault location is robust against ambient conditions as well as inherent inaccuracy of line parameters. The bisymmetry of the impedance matrix of the line is utilized to obtain a closed-form solution for fault location on short transmission lines. For long transmission lines, shunt capacitance of the line is taken into account to obtain an accurate closed-form estimation for fault location. Electromagnetic transient simulation in PSCAD/EMTDC environment validates the accuracy of the proposed fault-location method for a long untransposed 400-kV transmission line. The obtained results are also compared with an existing noniterative parameter-free fault-location method to demonstrate salient features of the proposed method.
引用
收藏
页码:1636 / 1644
页数:9
相关论文
共 46 条
[1]   A PRACTICAL APPROACH TO ACCURATE FAULT LOCATION ON EXTRA-HIGH-VOLTAGE TEED FEEDERS [J].
AGGARWAL, RK ;
COURY, DV ;
JOHNS, AT ;
KALAM, A ;
NILSSON, SL .
IEEE TRANSACTIONS ON POWER DELIVERY, 1993, 8 (03) :874-883
[2]  
Allen E. H., 2011, PACIFIC SW DISTURBAN
[3]  
[Anonymous], 2008, P 40 N AM POW S CALG
[4]  
[Anonymous], 2006, PSCAD EMTDC POW SYST
[5]  
[Anonymous], 1996, 600441 IEC
[6]  
[Anonymous], P IEEE C COMP VIS PA
[7]   A Novel Algorithm for Locating Faults on Transposed/Untransposed Transmission Lines Without Utilizing Line Parameters [J].
Apostolopoulos, Christos A. ;
Korres, George N. .
IEEE TRANSACTIONS ON POWER DELIVERY, 2010, 25 (04) :2328-2338
[8]   Disturbance recording in IEC 61850 substation automation systems [J].
Apostolov, A. .
2005/2006 IEEE/PES TRANSMISSION & DISTRIBUTION CONFERENCE & EXPOSITION, VOLS 1-3, 2006, :921-926
[9]   Locating Faults on Untransposed, Meshed Transmission Networks Using a Limited Number of Synchrophasor Measurements [J].
Azizi, Sadegh ;
Sanaye-Pasand, Majid ;
Paolone, Mario .
IEEE TRANSACTIONS ON POWER SYSTEMS, 2016, 31 (06) :4462-4472
[10]   Fault location on a transmission line using synchronized voltage measurements [J].
Brahma, SM ;
Girgis, AA .
IEEE TRANSACTIONS ON POWER DELIVERY, 2004, 19 (04) :1619-1622