Transmission power cables PD detection at damped AC voltages

被引:1
作者
Gulski, E [1 ]
Meijer, S [1 ]
Smit, JJ [1 ]
Wester, FJ [1 ]
Seitz, PN [1 ]
机构
[1] Delft Univ Technol, NL-2600 AA Delft, Netherlands
来源
CONFERENCE RECORD OF THE 2004 IEEE INTERNATIONAL SYMPOSIUM ON ELECTRICAL INSULATION | 2004年
关键词
D O I
10.1109/ELINSL.2004.1380645
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
This contribution presents new method for on-site PD diagnosis on HV transmission power cables. To on-site energize and to ignite partial discharges in transmission power cables, damped AC voltages up to 250 kV are generated. As a result, sensitive partial discharges detection and PD site location is possible. The developed system as well as PD measurements are shown to demonstrate the principles of this on-site diagnosis on HV transmission cables.
引用
收藏
页码:462 / 465
页数:4
相关论文
共 9 条
  • [1] BRETTSCHNEIDER S, P IEEE ISEI, P546
  • [2] FARNETI F, 1990, CIGRE SESS PAR
  • [3] Advanced partial discharge diagnostic of MV power cable system using oscillating wave test system
    Gulski, E
    Wester, FJ
    Smit, JJ
    Seitz, PN
    Turner, M
    [J]. IEEE ELECTRICAL INSULATION MAGAZINE, 2000, 16 (02) : 17 - 25
  • [4] GULSKI E, CIGR PAR 2004
  • [5] GULSKI E, CIGR PAR 2002
  • [6] HAUSCHILD W, CIGRE 2002, P33
  • [7] Kreuger F.H., 1995, IND HIGH 600 VOLTAGE
  • [8] LEFEVRE W, CIRED 1989 PAR FRANC, P270
  • [9] WESTER FJ, 2000, 16 CIRED 2001 AMST N, V16, P17