Precise fault location algorithm for double-circuit transmission lines using unsynchronised measurements from two anti-parallel ends

被引:16
作者
Korres, G. N. [1 ]
Apostolopoulos, C. A. [1 ]
机构
[1] Natl Tech Univ Athens, Dept Elect & Comp Engn, Athens 15780, Greece
关键词
20;
D O I
10.1049/iet-gtd.2009.0533
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
A new fault location algorithm for double-circuit transmission lines with availability of complete measurements from two anti-parallel end of the line is presented. Sequence voltage and current phasors from these ends are taken as inputs and no synchronisation between them is needed. Using the pre-fault data, the synchronisation angles between measurements at the reference and the anti-parallel ends are obtained. Using the fault data, the faulted circuit is determined and the sequence voltages and currents at the fault point are calculated as a function of the fault distance. Finally, using the fault boundary conditions that exist for a given fault type, the fault location is derived and solved by an iterative method. Owing to zero-sequence mutual coupling, it is not straightforward to express the zero-sequence voltage and current at the fault point as a function of the zero-sequence voltages and currents at the two measuring ends and the distance to fault. To overcome this problem, a modal transformation matrix is introduced to obtain the modal networks, which are decoupled and can be analysed independently. Based on distributed parameter line model, the proposed algorithm fully considers the effects of shunt capacitances and thus achieves superior locating accuracy, especially for long lines. Mutual coupling between circuits, source impedances and fault resistance do not influence the locating accuracy of the algorithm. The simulation results using ATP-EMTP and MATLAB demonstrate the effectiveness and accuracy of the proposed algorithm.
引用
收藏
页码:824 / 835
页数:12
相关论文
共 20 条
[1]   A useful methodology for analyzing distance relays performance during simple and inter-circuit faults in multi-circuit lines [J].
Agrasar, M ;
Uriondo, F ;
Hernandez, JR ;
Alvarez, R .
IEEE TRANSACTIONS ON POWER DELIVERY, 1997, 12 (04) :1465-1471
[2]  
Ahn YJ, 2000, 2000 IEEE POWER ENGINEERING SOCIETY SUMMER MEETING, CONFERENCE PROCEEDINGS, VOLS 1-4, P1344, DOI 10.1109/PESS.2000.868719
[3]  
[Anonymous], P 33 ANN W PROT REL
[4]  
Dommel H.W., 1992, EMTP Theory Book, V2nd ed.
[5]   Digital fault location for parallel double-circuit multi-terminal transmission lines [J].
Funabashi, T ;
Otoguro, H ;
Mizuma, Y ;
Dube, L ;
Ametani, A .
IEEE TRANSACTIONS ON POWER DELIVERY, 2000, 15 (02) :531-537
[6]  
Grainger J.J, 1994, POWER SYSTEM ANAL
[7]  
*IEEE, 1991, C371111991 IEEE
[8]   Locating faults in parallel transmission lines under availability of complete measurements at one end [J].
Izykowski, J ;
Rosolowski, E ;
Saha, MM .
IEE PROCEEDINGS-GENERATION TRANSMISSION AND DISTRIBUTION, 2004, 151 (02) :268-273
[9]   ACCURATE FAULT LOCATION TECHNIQUE FOR POWER TRANSMISSION-LINES [J].
JOHNS, AT ;
JAMALI, S .
IEE PROCEEDINGS-C GENERATION TRANSMISSION AND DISTRIBUTION, 1990, 137 (06) :395-402
[10]  
Kasztenny B., 2000, P 53 ANN C PROT REL, P1