Single-Loop Digital Control of High-Power 400-Hz Ground Power Unit for Airplanes

被引:117
作者
Li, Zixin [1 ]
Li, Yaohua [1 ]
Wang, Ping [1 ]
Zhu, Haibin [1 ]
Liu, Congwei [1 ]
Gao, Fanqiang [1 ]
机构
[1] Chinese Acad Sci, Inst Elect Engn, Beijing 100190, Peoples R China
关键词
Digital control; resonant controller; single-loop control; 400-Hz inverter; COMPENSATE UNBALANCE; HARMONIC DISTORTION; CONTROL STRATEGY; DOMAIN ANALYSIS; UPS; FRAME; ERROR;
D O I
10.1109/TIE.2009.2033490
中图分类号
TP [自动化技术、计算机技术];
学科分类号
0812 ;
摘要
In this paper, the influence of one-sample delay for sampling and computation in digital control on the bandwidth of the inner current loop of a 400-Hz ground power unit (GPU) is analyzed first. The results show that it is difficult and even impossible for high-power 400-Hz GPUs to maintain low total harmonic distortion content in the output voltage with the conventional proportional-integral-based double-loop control. To improve the performance, resonant controllers with parallel structure which are widely used in active power filters are applied to the single-loop control of the 400-Hz GPU. The parameter design criterion for the parallel resonant controllers is discussed in the discrete time domain. Meanwhile, adoption of proportional gain in the single-loop control is investigated. The results show that it can improve the performance little and may cause instability problems. Comparisons between different control methods for the 400-Hz GPU are also made, and the single-loop control method in this paper seems to be the most suitable one in terms of simplicity and performance. Experiments on a 16-b fixed-point DSP-controlled 90-kVA 400-Hz GPU prototype show satisfactory results of the single-loop method feeding linear/nonlinear and balanced/unbalanced loads.
引用
收藏
页码:532 / 543
页数:12
相关论文
共 22 条
[1]   Current control strategy for power conditioners using sinusoidal signal integrators in synchronous reference frame [J].
Bojoi, RI ;
Griva, G ;
Bostan, V ;
Guerriero, M ;
Farina, F ;
Profumo, F .
IEEE TRANSACTIONS ON POWER ELECTRONICS, 2005, 20 (06) :1402-1412
[2]   A simple control method for high-performance UPS inverters through output-impedance reduction [J].
Deng, Heng ;
Oruganti, Ramesh ;
Srinivasan, Dipti .
IEEE TRANSACTIONS ON INDUSTRIAL ELECTRONICS, 2008, 55 (02) :888-898
[3]   An adaptive control for UPS to compensate unbalance and harmonic distortion using a combined capacitor/load current sensing [J].
Escobar, G. ;
Mattavelli, P. ;
Stankovic, A. M. ;
Valdez, Andres A. ;
Leyva-Ramos, Jesus .
IEEE TRANSACTIONS ON INDUSTRIAL ELECTRONICS, 2007, 54 (02) :839-847
[4]   Repetitive. based controller for a UPS inverter to compensate unbalance and harmonic distortion [J].
Escobar, G. ;
Valdez, A. A. ;
Leyva-Ramos, J. ;
Mattavelli, P. .
IEEE TRANSACTIONS ON INDUSTRIAL ELECTRONICS, 2007, 54 (01) :504-510
[5]  
GENE JDP, 1997, DIGITAL CONTROL DYNA
[6]  
Heng Deng, 2005, IEEE Power Electronics Letters, V3, P1, DOI 10.1109/LPEL.2004.842402
[7]   A new control method for 400-Hz ground power units for airplanes [J].
Jensen, UB ;
Blaabjerg, F ;
Pedersen, JK .
IEEE TRANSACTIONS ON INDUSTRY APPLICATIONS, 2000, 36 (01) :180-187
[8]  
JENSEN UB, 2000, THESIS AALBORG U AAL