Influence of current transformer saturation on line current differential protection algorithms

被引:27
作者
Gangadharan, P. K.
Sidhu, T. S.
Klimek, A.
机构
[1] Univ Western Ontario, Dept Elect & Comp Engn, London, ON N6A 5B9, Canada
[2] Areva T&D UK Ltd, Stafford ST17 4LX, England
关键词
D O I
10.1049/iet-gtd:20060138
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
The performance of line current differential protection algorithms during current transformer (CT) saturation is analysed. The study covers popularly used algorithms and presents their degree of immunity to CT saturation. The degree of error in phasor measurement due to CT saturation is estimated through simulation studies and this information is used to decide the CT dimensioning for the relay.