Probabilistic optimal design of cleanroom air-conditioning systems facilitating optimal ventilation control under uncertainties

被引:20
作者
Zhuang, Chaoqun [1 ]
Wang, Shengwei [1 ]
Shan, Kui [1 ]
机构
[1] Hong Kong Polytech Univ, Dept Bldg Serv Engn, Kowloon, Hong Kong, Peoples R China
关键词
Probabilistic optimal design; Optimal ventilation strategy; Design optimization; Air-conditioning system; Uncertainty; ENERGY-CONSUMPTION; COOLING SYSTEMS; UNIT MAU; PERFORMANCE; MODELS; EFFICIENCY; BUILDINGS; BEHAVIOR;
D O I
10.1016/j.apenergy.2019.113576
中图分类号
TE [石油、天然气工业]; TK [能源与动力工程];
学科分类号
0807 ; 0820 ;
摘要
Buildings with spaces requiring strict temperature and humidity controls, such as pharmaceutical cleanrooms and semiconductor/microchip factories, have been growing very quickly in terms of total floor area and energy consumption. In such buildings, much of the energy is unnecessarily wasted due to the incoordination of system design and operation/control, especially under "off-design" and ever-changing ambient and load conditions. This paper, therefore, proposes a probabilistic optimal design method for cleanroom air-conditioning systems facilitating optimal ventilation control under uncertainties. To consider the effects of asynchronous loads in different zones/spaces with reduced computation demand, a probabilistic diversity factor method is proposed which is a simplified method to quantify the effects of uncertainties of space load diversities in multiple zones/spaces using diversity factors. The proposed design method is implemented and validated in the design optimization of air-conditioning systems for implementing four different ventilation control strategies considering possible and uncertain off-design conditions. The energy and economic performance as well as service satisfaction of the air-conditioning systems are also evaluated and compared. Results show that the proposed design method can obtain the optimal air-conditioning systems with minimum life-cycle cost and superior satisfaction of service.
引用
收藏
页数:15
相关论文
共 58 条
  • [51] Stochastic models for building energy prediction based on occupant behavior assessment
    Virote, Joao
    Neves-Silva, Rui
    [J]. ENERGY AND BUILDINGS, 2012, 53 : 183 - 193
  • [52] Vose MD, 1999, COM ADAP SY
  • [53] Minimum Kolmogorov-Smirnov test statistic parameter estimates
    Weber, MD
    Leemis, LM
    Kincaid, RK
    [J]. JOURNAL OF STATISTICAL COMPUTATION AND SIMULATION, 2006, 76 (03) : 195 - 206
  • [54] Wu XP, 1997, APPL THERM ENG, V17, P561, DOI 10.1016/S1359-4311(96)00058-0
  • [55] Xu T., 2003, IEST P 49 ANN TECHN
  • [56] A systematic procedure to study the influence of occupant behavior on building energy consumption
    Yu, Zhun
    Fung, Benjamin C. M.
    Haghighat, Fariborz
    Yoshino, Hiroshi
    Morofsky, Edward
    [J]. ENERGY AND BUILDINGS, 2011, 43 (06) : 1409 - 1417
  • [57] Influence of asynchronous demand behavior on overcooling in multiple zone AC systems
    Zhou, Xin
    Yan, Da
    Jiang, Yi
    Shi, Xing
    [J]. BUILDING AND ENVIRONMENT, 2016, 110 : 65 - 75
  • [58] Adaptive full-range decoupled ventilation strategy and air-conditioning systems for cleanrooms and buildings requiring strict humidity control and their performance evaluation
    Zhuang, Chaoqun
    Wang, Shengwei
    Shan, Kui
    [J]. ENERGY, 2019, 168 : 883 - 896