Insulation Characteristics of GIS Epoxy Insulators with Non-uniform Surface Resistance under DC Voltage

被引:11
|
作者
Okabe, Shigemitsu [1 ]
Ueta, Genyo [1 ]
Nojima, Kenichi [2 ]
机构
[1] Tokyo Elect Power Co Ltd, Tsurumi Ku, Yokohama, Kanagawa 2308510, Japan
[2] Toshiba Co Ltd, Kawasaki Ku, Kawasaki, Kanagawa 2100862, Japan
关键词
Gas insulated switchgear (GIS); epoxy insulator; dc voltage; surface resistance; SF6; gas; insulation characteristic; transient electric field analysis; lightning impulse voltage test; SF6; GAS; SPACERS; MECHANISM;
D O I
10.1109/TDEI.2014.004513
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
Now that gas-insulated switchgear (GIS) for ac systems are becoming increasingly compact as specifications are rationalized, more consideration of their insulation characteristics for residual dc voltage is required. Furthermore, with dc power transmission technology drawing more and more global attention, clarifying the insulation characteristics of GIS for dc voltage is increasingly important. For GIS insulating epoxy spacer, the present paper experimentally and analytically studied the influence of spacer surface condition on dc withstand voltage performance. In specific terms, initially, an insulating spacer model with an area of non-uniform resistivity present in the surface layer was created and the dc voltage breakdown characteristics were obtained. As a result, it was clarified that the time delay to breakdown increased with lowering the applied voltage, or in other words, even if a low voltage was applied, breakdown may occur after an extended period. Subsequently, using the same non-uniform resistivity model, the change in the electric field distribution over time under dc voltage was investigated through transient electric field analysis. Consequently, it was found that the electric field distribution varied from a capacitive to a resistive field and the maximum electric field was generated in the boundary between the high-and low-resistivity areas. It was further clarified, based on these breakdown characteristics and electric field analytical results, that the presence of an area of non-uniform resistivity on the insulating spacer creepage surface caused electric field concentration over time and breakdown occurred if the electric field in the creepage surface direction exceeded 40 kV/mm or so. Moreover, the breakdown characteristics were investigated where a lightning impulse voltage was superimposed over a dc voltage. Consequently, the creepage breakdown electric field where a dc voltage was applied alone was almost identical to that where the superimposed voltage was applied. It means that the application of the superimposed voltage may potentially allow the insulating spacer withstand voltage performance to be evaluated by a shorter time test for a dc voltage alone or the dc voltage with a superimposed VFTO.
引用
收藏
页码:516 / 525
页数:10
相关论文
共 50 条
  • [22] Study on Partial Discharge Characteristics of Severe Non-uniform Electric Field in SF6 Under Negative DC Voltage
    Pang P.
    Sun Z.
    Zhang Q.
    Han X.
    Hou Z.
    Li J.
    Gaodianya Jishu/High Voltage Engineering, 2019, 45 (04): : 1093 - 1100
  • [23] MEASURING THE INSULATION RESISTANCE OF DC LINES UNDER OPERATING VOLTAGE
    UGRYUMOV, EP
    REDKIN, VA
    MEASUREMENT TECHNIQUES USSR, 1989, 32 (04): : 362 - 366
  • [24] Distribution characteristics of electric potential and electric field along HV insulators under non-uniform contamination
    Mao D.
    Tang Q.
    Gao Q.
    Lixue Xuebao/Chinese Journal of Theoretical and Applied Mechanics, 2020, 52 (03): : 698 - 706
  • [25] Metal nanoparticle-doped epoxy resin to suppress surface charge accumulation on insulators under DC voltage
    Wang, Tian-Yu
    Zhang, Bo-Ya
    Li, Da-Yu
    Hou, Yi-Cen
    Zhang, Gui-Xin
    NANOTECHNOLOGY, 2020, 31 (32)
  • [26] Metal inserted spacer influence on particle motion in non-uniform electrical field under DC voltage
    Jia, J
    Zhang, Q
    Zhu, J
    Yang, L
    Proceedings of the 2005 International Symposium on Electrical Insulating Materials, Vols, 1-3, 2005, : 372 - 375
  • [27] Influence of non-uniform hydrophobicity distribution on pollution flashover characteristics of composite insulators
    Yu, Xinzhe
    Zhang, Qiaogen
    Yang, Xiaolei
    Yang, Hao
    Zhou, Jun
    Liu, Bo
    IET SCIENCE MEASUREMENT & TECHNOLOGY, 2018, 12 (08) : 1009 - 1014
  • [28] The phenomena and characteristics of oil-paper insulation surface discharge under AC and DC voltage
    Qi, Bo
    Wei, Zhen
    Li, Chengrong
    Yuan, Qing
    Gao, Yi
    Zhang, Xiaohan
    Diangong Jishu Xuebao/Transactions of China Electrotechnical Society, 2016, 31 (10): : 59 - 67
  • [29] Effect of Isolation Mode and Surface Condition of an Insulating Barrier on the Performance of a Non-uniform Field Electrode System under Positive DC Voltage
    Boudissa, Rabah
    Merabet, Samia
    Iouknane, Saloua
    Bayadi, Abdelhafid
    IEEE TRANSACTIONS ON DIELECTRICS AND ELECTRICAL INSULATION, 2013, 20 (05) : 1523 - 1529
  • [30] Investigation and analysis of AC flashover voltage of SiR insulators under longitudinal and fan-shaped non-uniform pollutions
    Samakosh, Jaber Dadashizadeh
    Mirzaie, Mohammad
    INTERNATIONAL JOURNAL OF ELECTRICAL POWER & ENERGY SYSTEMS, 2019, 108 : 382 - 391