Impact of load characteristics and low-voltage load shedding schedule on dynamic voltage stability

被引:0
作者
Li, Huawei [1 ]
Fan, Yu [1 ]
Wu, Tao [2 ]
机构
[1] Beijing Jiaotong Univ, Sch Elect Engn, Beijing 100044, Peoples R China
[2] North China Elect Power Res Inst, Beijing 100045, Peoples R China
来源
2006 CANADIAN CONFERENCE ON ELECTRICAL AND COMPUTER ENGINEERING, VOLS 1-5 | 2006年
关键词
power grid; Dynamic voltage stability; Dynamic characteristics of load; Low-voltage load shedding schedule; Low-frequency load shedding schedule; R TDS;
D O I
暂无
中图分类号
TP18 [人工智能理论];
学科分类号
081104 ; 0812 ; 0835 ; 1405 ;
摘要
The impact of load characteristics and the low-voltage load shedding schedule on dynamic voltage stability is studied for part of the power grid in Beijing. The research is conducted on a Real-Time Digital Simulation (RTDS) system and based on the projected data for the power grid in the Northern China Region. We show that under severe shortage of active power, the larger proportion of asynchronous motors in the total load is, the more likely voltage collapses; while the larger proportion of fixed impedance in the total load is, the more likely frequency collapses. Therefore, load characteristics has significant impact on the voltage stability. Proper application of the low-voltage load shedding schedule will improve the power grid stability.
引用
收藏
页码:402 / +
页数:3
相关论文
共 9 条
[1]  
Cheng Haozhong, 1998, Automation of Electric Power Systems, V22, P50
[2]  
He Renmu, 1998, Automation of Electric Power Systems, V22, P9
[3]  
Liu Wenying, 2004, Automation of Electric Power Systems, V28, P74
[4]  
*N CHIN EL POW TEC, 2002, UNPUB STUD LOW VOLT
[5]  
WU T, 2002, N CHINA ELECT PO AUG, P4
[6]  
Xu Taishan, 1999, Automation of Electric Power Systems, V23, P9
[7]  
Yu Yixin, 1999, Automation of Electric Power Systems, V23, P1
[8]  
YU YX, 1999, THEOREM METHODOLOGY
[9]   Loss of SHP-1 phosphatase alters cytokine expression in the mouse hindbrain following cochlear ablation [J].
Zhao, H ;
Lurie, DI .
CYTOKINE, 2004, 28 (01) :1-9