Comparison of evaluation methods of the small current breaking performance for SF6 gas circuit breakers

被引:0
作者
Song, KD [1 ]
Lee, BY [1 ]
Park, KY [1 ]
Shin, YJ [1 ]
机构
[1] Korea Electrotechnol Res Inst, Chang Won, South Korea
来源
IEEE/PES TRANSMISSION AND DISTRIBUTION CONFERENCE AND EXHIBITION 2002: ASIA PACIFIC, VOLS 1-3, CONFERENCE PROCEEDINGS: NEW WAVE OF T&D TECHNOLOGY FROM ASIA PACIFIC | 2002年
关键词
SF6 gas circuit breaker; dielectric recovery; small current interruption; shock wave; arcing contacts;
D O I
暂无
中图分类号
TE [石油、天然气工业]; TK [能源与动力工程];
学科分类号
0807 ; 0820 ;
摘要
Circuit breakers have to possess both the small current and the large current interruption capabilities. The need has been constantly increased to evaluate the current interruption performance without resort to the short-circuit tests to save time and expenses during the development of gas circuit breakers. The increasing reliability of the analysis schemes and the dramatically increased computing speed have made it possible to evaluate them from the computer simulation results to some extent. The objective of this paper is to estimate the small current interruption performance of SF6 gas circuit breakers and to compare the results from various methods. In order to evaluate the dielectric recovery strength of gas circuit breakers for small current interruption, two methods have been usually utilized. One is the empirical formula obtained from a series of tests and the other is the theoretical formula obtained from streamer theory. In this paper, both methods were applied to predict the small current interruption capability of model circuit breakers and were investigated in terms of the accuracy by comparing the simulation results with test ones.
引用
收藏
页码:413 / 418
页数:6
相关论文
共 14 条
[1]   DIELECTRIC RECOVERY OF AN AXIALLY BLOWN SF6-ARC AFTER CURRENT ZERO .3. COMPARISON OF EXPERIMENT AND THEORY [J].
BRAND, KP ;
EGLI, W ;
NIEMEYER, L ;
RAGALLER, K ;
SCHADE, E .
IEEE TRANSACTIONS ON PLASMA SCIENCE, 1982, 10 (03) :162-172
[2]  
ENDO F, 1989, IEEE T POWER DELIVER, V89, P1731
[3]  
Greenwood A., 1991, ELECT TRANSIENTS POW, P92
[4]  
*IEC, 1998, 56 IEC, P191
[5]  
*IEC, 1999, 60056CDV IEC, P111
[6]   DIELECTRIC WITHSTAND AND BREAKING CAPACITY OF SF6 CIRCUIT-BREAKERS AT LOW-TEMPERATURES [J].
LANDRY, M ;
STJEAN, G ;
JEANJEAN, R ;
DEMISSY, D .
IEEE TRANSACTIONS ON POWER DELIVERY, 1988, 3 (03) :1029-1035
[7]  
ONCHI T, 2000, P 13 INT C GAS DISCH, V1, P42
[8]   CRITERIA FOR SPARK BREAKDOWN IN SULFUR HEXAFLUORIDE [J].
PEDERSEN, A .
IEEE TRANSACTIONS ON POWER APPARATUS AND SYSTEMS, 1970, PA89 (08) :2043-&
[9]   DIELECTRIC RECOVERY OF AN AXIALLY BLOWN SF6-ARC AFTER CURRENT ZERO .2. THEORETICAL INVESTIGATIONS [J].
RAGALLER, K ;
EGLI, W ;
BRAND, KP .
IEEE TRANSACTIONS ON PLASMA SCIENCE, 1982, 10 (03) :154-162
[10]   DIELECTRIC RECOVERY OF AN AXIALLY BLOWN SF6-ARC AFTER CURRENT ZERO .1. EXPERIMENTAL INVESTIGATIONS [J].
SCHADE, E ;
RAGALLER, K .