Transient Stability Enhancement Control Strategy Based on Improved PLL for Grid Connected VSC during Severe Grid Fault

被引:48
作者
Liu, Yuan [1 ]
Yao, Jun [1 ]
Pei, Jinxin [1 ]
Zhao, Yang [1 ]
Sun, Peng [1 ]
Zeng, Deiyin [1 ]
Chen, Shiyue [1 ]
机构
[1] Chongqing Univ, State Key Lab Power Transmiss Equipment & Syst Se, Sch Elect Engn, Chongqing 400044, Peoples R China
基金
中国国家自然科学基金;
关键词
Damping; Power system stability; Stability analysis; Synchronization; Mathematical model; Transient analysis; Phase locked loops; Damping ratio; Grid fault; Phase-locked loop; Transient stability; Voltage source converters;
D O I
10.1109/TEC.2020.3011203
中图分类号
TE [石油、天然气工业]; TK [能源与动力工程];
学科分类号
0807 ; 0820 ;
摘要
In this article, the transient synchronization process of the grid-connected voltage source converters (VSC) is studied detailly. Firstly, the phase-locked loop (PLL)-synchronized VSC is modeled according to the rotor motion equation of synchronous generator (SG). Furthermore, the VSC's damping ratio is derived, and the effects of the VSC's control parameters and the operation status on the equivalent power angle (EPA) is investigated. Moreover, the influence of the PLL's parameters and the voltage dips degree on the VSC's transient frequency behavior are analyzed. Analysis result reveals that the VSC's damping ratio decreases once the grid voltage drops, so that the EPA and frequency of the VSC may appear large overshoot and oscillation, which may trigger the frequency protection and deteriorate the VSC's transient stability. In order to ensure that the VSC can smoothly operate to new equilibrium points, an improved PLL is proposed, which can adaptively adjust the VSC's damping ratio for different voltage sags. The proposed method can not only reduce the overshoot of the EPA but also restrain the VSC's frequency dips degree. Finally, the simulations and experimental tests validate the effectiveness of the theoretical analysis.
引用
收藏
页码:218 / 229
页数:12
相关论文
共 27 条
[1]  
[Anonymous], 199632011 GBT
[2]   Overview of control and grid synchronization for distributed power generation systems [J].
Blaabjerg, Frede ;
Teodorescu, Remus ;
Liserre, Marco ;
Timbus, Adrian V. .
IEEE TRANSACTIONS ON INDUSTRIAL ELECTRONICS, 2006, 53 (05) :1398-1409
[3]   Mechanism Analysis of DFIG-Based Wind Turbinex2019;s Fault Current During LVRT With Equivalent Inductances [J].
Chang, Yuanzhu ;
Hu, Jiabing ;
Yuan, Xiaoming .
IEEE JOURNAL OF EMERGING AND SELECTED TOPICS IN POWER ELECTRONICS, 2020, 8 (02) :1515-1527
[4]   A phase tracking system for three phase utility interface inverters [J].
Chung, SK .
IEEE TRANSACTIONS ON POWER ELECTRONICS, 2000, 15 (03) :431-438
[5]   Analysis of Phase-Locked Loop Low-Frequency Stability in Three-Phase Grid-Connected Power Converters Considering Impedance Interactions [J].
Dong, Dong ;
Wen, Bo ;
Boroyevich, Dushan ;
Mattavelli, Paolo ;
Xue, Yaosuo .
IEEE TRANSACTIONS ON INDUSTRIAL ELECTRONICS, 2015, 62 (01) :310-321
[6]  
E. ON NETZ GmbH, 2006, GRID CODE HIGH EXTRA
[7]   Impacts of High Penetration of DFIG Wind Turbines on Rotor Angle Stability of Power Systems [J].
Edrah, Mohamed ;
Lo, Kwok L. ;
Anaya-Lara, Olimpo .
IEEE TRANSACTIONS ON SUSTAINABLE ENERGY, 2015, 6 (03) :759-766
[8]   Synchronization and Reactive Current Support of PMSG-Based Wind Farm During Severe Grid Fault [J].
Geng, Hua ;
Liu, Lu ;
Li, Ruiqi .
IEEE TRANSACTIONS ON SUSTAINABLE ENERGY, 2018, 9 (04) :1596-1604
[9]  
Givaki K., 2015, P INT C REN POW GEN, P1, DOI [10.1049/cp.2015.0440, DOI 10.1049/CP.2015.0440]
[10]   Instability of Wind Turbine Converters During Current Injection to Low Voltage Grid Faults and PLL Frequency Based Stability Solution [J].
Goksu, Omer ;
Teodorescu, Remus ;
Bak, Claus Leth ;
Iov, Florin ;
Kjaer, Philip Carne .
IEEE TRANSACTIONS ON POWER SYSTEMS, 2014, 29 (04) :1683-1691