Analysis of Thermal Performance Metrics-Application to CPU Cooling in HPC Servers

被引:8
作者
Guggari, Shrishail I. [1 ,2 ]
机构
[1] Atos Bull India Design Ctr, Bengaluru 560048, India
[2] Acad Sci & Innovat Res AcSIR, Ghaziabad 201002, India
来源
IEEE TRANSACTIONS ON COMPONENTS PACKAGING AND MANUFACTURING TECHNOLOGY | 2021年 / 11卷 / 02期
关键词
Heat sinks; Cooling; Thermal resistance; Resistance; Cold plates; Heat transfer; Measurement; Central processing unit (CPU); cold plate; cooling; effectiveness; heatsink; optimization; thermal resistance;
D O I
10.1109/TCPMT.2020.3029940
中图分类号
T [工业技术];
学科分类号
08 ;
摘要
Optimization of heatsinks has a critical importance for the energy-efficient cooling of high-performance computing (HPC) servers to meet reliability, performance, and cost targets. This article provides a detailed application of the effectiveness as a performance metric to provide a qualitative comparison of the CPU heatsink solutions. First, the use of effectiveness as a metric to provide an absolute performance of heatsinks on a simple scale of 0-1 is highlighted. Then, the effectiveness and thermal resistances are compared to explore the limits of air cooling and the relative merits of liquid cooling. Second, a response surface method (RSM) for the heatsink optimization is presented. Furthermore, a response surface optimization (RSO) based on the design of experiments (DOE) is performed on the numerical models of the heatsink and cold plates using FloTHERM computational fluid dynamics (CFD) software. The simulation results obtained at 45 degrees C inlet are used to provide an objective comparison among the optimum heatsink and cold plates. The simulations show that heatsinks have the effectiveness of 0.65-0.75 and a cooling capability of 150-250 W. The cold plates have an effectiveness of 0.25-0.30 and a cooling capability of 325-425 W. Furthermore, the simulation results are compared with benchmark validation studies. Counterintuitively, the higher effectiveness obtained for the air-cooled heatsinks indicates limited scope for further improvement, whereas the cold plates (with lower effectiveness) provide great scope for further improvements to meet future cooling challenges.
引用
收藏
页码:222 / 232
页数:11
相关论文
共 23 条
  • [1] [Anonymous], 2019, FLOTHERM V19 1 SIMCE
  • [2] [Anonymous], 2012, JESD511201
  • [3] ASHRAE Technical Committee (TC), 2016, CISC VIS NETW IND GL
  • [4] Copeland D., 2005, ELECT COOLING, V11
  • [5] Ellsworth M. J., 2015, P INT EL PACK TECH C, P1
  • [6] Galloway J, 2011, P IEEE SEMICOND THER, P181, DOI 10.1109/STHERM.2011.5767197
  • [7] Electronics Thermal Management in Information and Communications Technologies: Challenges and Future Directions
    Garimella, Suresh V.
    Persoons, Tim
    Weibel, Justin A.
    Gektin, Vadim
    [J]. IEEE TRANSACTIONS ON COMPONENTS PACKAGING AND MANUFACTURING TECHNOLOGY, 2017, 7 (08): : 1191 - 1205
  • [8] Liquid Cooling of Compute System
    Gullbrand, Jessica
    Luckeroth, Mark J.
    Sprenger, Mark E.
    Winkel, Casey
    [J]. JOURNAL OF ELECTRONIC PACKAGING, 2019, 141 (01)
  • [9] Performance Analysis and Shape Optimization of an Impingement Microchannel Cold Plate
    Hadad, Yaser
    Fallahtafti, Najmeh
    Choobineh, Leila
    Hoang, Cong Hiep
    Radmard, Vahideh
    Chiarot, Paul R.
    Sammakia, Bahgat
    [J]. IEEE TRANSACTIONS ON COMPONENTS PACKAGING AND MANUFACTURING TECHNOLOGY, 2020, 10 (08): : 1304 - 1319
  • [10] Kays W.M., 1984, COMPACT HEAT EXCHANG, V3rd