Modeling and measurements of electric fields in composite oil/cellulose insulation

被引:8
作者
Gafvert, Uno [1 ,1 ]
Hjortstam, Olof [1 ]
Serdyuk, Yuriy [2 ]
Tornkvist, Christer [1 ]
Walfridsson, Lars [1 ]
机构
[1] ABB Corp Res, Vasteras, Sweden
[2] Chalmers, Gothenburg, Sweden
来源
2006 ANNUAL REPORT CONFERENCE ON ELECTRICAL INSULATION AND DIELECTRIC PHENOMENA | 2006年
关键词
D O I
10.1109/CEIDP.2006.312084
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
In this paper we report on basic studies of the electric fields under dc stress in a composite insulation consisting of transformer oil and oil-impregnated pressboard, typical for HVDC converter transformers. The time dependent electrical fields in our model geometry are measured using electro-optic Kerr method, and theoretically studied with an ion drift-diffusion conduction model. The measured and calculated electrical fields are compared and analyzed.
引用
收藏
页码:154 / 157
页数:4
相关论文
共 8 条