An efficient geometric parameterization technique for the continuation power flow

被引:18
作者
Garbelini, Enio
Alves, Dilson A.
Neto, Alfredo B.
Righeto, Edson
da Silva, Luiz C. P.
Castro, Carlos A.
机构
[1] Univ Estadual Paulista, CISA, Fac Elect Engn, Dept Elect Engn, BR-15378000 Sao Paulo, Brazil
[2] Univ Estadual Campinas, Sch Elect & Comp Engn, BR-13081970 Campinas, SP, Brazil
基金
巴西圣保罗研究基金会;
关键词
continuation methods; voltage collapse; load flow; multiple solutions; maximum loading point;
D O I
10.1016/j.epsr.2006.02.002
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
Continuation methods have been shown as efficient tools for solving ill-conditioned cases, with close to singular Jacobian matrices, such as the maximum loading point of power systems. Some parameterization techniques have been proposed to avoid matrix singularity and successfully solve those cases. This paper presents a new geometric parameterization scheme that allows the complete tracing of the P-V curves without ill-conditioning problems. The proposed technique associates robustness to simplicity and, it is of easy understanding. The Jacobian matrix singularity is avoided by the addition of a line equation, which passes through a point in the plane determined by the total real power losses and loading factor. These two parameters have clear physical meaning. The application of this new technique to the IEEE systems (14, 30, 57, 118 and 300 buses) shows that the best characteristics of the conventional Newton's method are not only preserved but also improved. (C) 2006 Elsevier B.V. All rights reserved.
引用
收藏
页码:71 / 82
页数:12
相关论文
共 23 条
[11]   Stability limit and uniqueness of voltage solutions for radial power networks [J].
Chen, JF ;
Wang, WM .
ELECTRIC MACHINES AND POWER SYSTEMS, 1997, 25 (03) :247-261
[12]   CPFLOW - A PRACTICAL TOOL FOR TRACING POWER-SYSTEM STEADY-STATE STATIONARY BEHAVIOR DUE TO LOAD AND GENERATION VARIATIONS [J].
CHIANG, HD ;
FLUECK, AJ ;
SHAH, KS ;
BALU, N .
IEEE TRANSACTIONS ON POWER SYSTEMS, 1995, 10 (02) :623-630
[13]  
Gao B, 1996, IEEE T POWER SYST, V11, P1314, DOI 10.1109/59.535672
[14]  
Hua Li, 1999, 1999 IEEE Power Engineering Society Summer Meeting. Conference Proceedings (Cat. No. 99CH36364), P647, DOI 10.1109/PESS.1999.787393
[15]   CALCULATION OF CRITICAL LOADING CONDITION WITH NOSE CURVE USING HOMOTOPY CONTINUATION METHOD [J].
IBA, K ;
SUZUKI, H ;
EGAWA, M ;
WATANABE, T .
IEEE TRANSACTIONS ON POWER SYSTEMS, 1991, 6 (02) :584-593
[16]  
LONG B, 1996, P 28 N AM POW S, P8
[17]  
Mansour Y., 1993, IEEE Power Engineering Subcommittee Report 93TH0620-5- PWR
[18]   Effective calculation of power system low-voltage solutions [J].
Overbye, TJ ;
Klump, RP .
IEEE TRANSACTIONS ON POWER SYSTEMS, 1996, 11 (01) :75-80
[19]   AUTOMATIC ADJUSTMENT OF TRANSFORMER AND PHASE-SHIFTER TAPS IN NEWTON POWER FLOW [J].
PETERSON, NM ;
MEYER, WS .
IEEE TRANSACTIONS ON POWER APPARATUS AND SYSTEMS, 1971, PA90 (01) :103-&
[20]  
*REACT POW RES WOR, 1999, FIN REP VOLT STAB CR, P154