SYSTEM SIMULATION FOR AN UNTREATED SEWAGE SOURCE HEAT PUMP (USSHP) IN WINTER

被引:0
作者
Qin, Na [1 ]
Hao, Peng Z. [2 ]
机构
[1] Tianjin Univ Technol, Dept Thermal Engn, Control Theory & Applicat Complex Syst Tianjin Ke, 391 West Binshui St, Xiqing Dist 300384, Peoples R China
[2] Tianjin Inst Urban Construct, Dept Elect & Informat Engn, 391 Jinjing Rd, Xiqing Dist 300384, Peoples R China
来源
SEVENTH INTERNATIONAL CONFERENCE ON ELECTRONICS AND INFORMATION ENGINEERING | 2017年 / 10322卷
关键词
untreated sewage source heat pump; direct mode; sewage inlet temperature; WASTE-WATER; ENERGY;
D O I
10.1117/12.2265269
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
The paper discusses the system characteristics of an untreated sewage source heat pump in winter. In this system, the sewage enters into the evaporator directly. The variable parameters to control the system contain the sewage temperature at evaporator inlet and the water temperature at condenser inlet. It is found that most parameters, except the condensation heat transfer coefficient, change in the form of sine wave the same as the sewage temperature at inlet. The heating load and consumed power are 12.9kW and 3.45kW when the sewage temperature at inlet is 13.. COP is about 3.75 in the range of the sewage temperature at inlet of 12-13 degrees C.