Experimental study of a novel household exhaust air heat pump enhanced by indirect evaporative cooling

被引:31
作者
Li, Wuyan [1 ]
Shi, Wenxing [1 ]
Wang, Jue [2 ]
Li, Yongcai [2 ]
Lu, Jun [2 ]
机构
[1] Tsinghua Univ, Sch Architecture, Dept Bldg Sci, Beijing 100084, Peoples R China
[2] Chongqing Univ, Sch Civil Engn, Chongqing 400045, Peoples R China
基金
中国国家自然科学基金;
关键词
Exhaust air heat pump; Indirect evaporative cooling; Heat recovery; Experimental test; Mechanical ventilation; ENERGY WHEEL EFFECTIVENESS; PERFORMANCE IMPROVEMENT; RECOVERY; SYSTEM; CONDENSER; COOLER; UNIT; HVAC;
D O I
10.1016/j.enbuild.2021.110808
中图分类号
TU [建筑科学];
学科分类号
0813 ;
摘要
This paper presents an experimental study of a novel household ventilator with exhaust air heat pump enhanced by indirect evaporative cooling. In this study, a prototype was made according to this theory and tested on the test rig. The test was carried out to evaluate the energy performance of the system during the cooling season. During the test, the thermal performances of the prototype under four different operating modes were comprehensively studied. In the typical summer conditions, the prototype operating as an indirect evaporative cooler followed by an evaporative condenser heat pump shows the highest cooling capacity at 4.27 kW and energy efficiency ratio (EER) at 5.12, which is a great performance improvement compared with that of conventional operating methods. The results of variable conditions tests show that this system can operate efficiently under different summer ambient conditions with the EER varying from 4.16 to 5.65. Besides, a comparison with other prototypes found in existing literature was also made in this study. Give consideration to compact and energy efficiency, the novel ventilation system shows a good academic value and application prospect in energy saving air-conditioning domain. (c) 2021 Elsevier B.V. All rights reserved.
引用
收藏
页数:12
相关论文
共 35 条
[1]   Performance study of the indirect evaporative air cooler and heat recovery exchanger in air conditioning system during the summer and winter operation [J].
Anisimov, Sergey ;
Pandelidis, Demis ;
Jedlikowski, Andrzej .
ENERGY, 2015, 89 :205-225
[2]   A novel packaged outdoor air dehumidifier with exhaust air heat pump Experiment and simulation [J].
Cao, Xiang ;
Yang, Chen ;
Sun, Zhao ;
Lu, Yue-Ming ;
Chang, Meng-Meng ;
Shao, Liang-Liang ;
Zhang, Chun-Lu .
APPLIED THERMAL ENGINEERING, 2020, 181
[3]   Parameter sensitivity analysis and configuration optimization of indirect evaporative cooler (IEC) considering condensation [J].
Chen, Yi ;
Yang, Hongxing ;
Luo, Yimo .
APPLIED ENERGY, 2017, 194 :440-453
[4]   Exhaust air heat recovery in buildings [J].
Fehrm, M ;
Reiners, W ;
Ungemach, M .
INTERNATIONAL JOURNAL OF REFRIGERATION-REVUE INTERNATIONALE DU FROID, 2002, 25 (04) :439-449
[5]   Experimental analysis of an air-to-air heat recovery unit for balanced ventilation systems in residential buildings [J].
Fernandez-Seara, Jose ;
Diz, Ruben ;
Uhia, Francisco J. ;
Dopazo, Alberto ;
Ferro, Jose M. .
ENERGY CONVERSION AND MANAGEMENT, 2011, 52 (01) :635-640
[6]   Energy analyses of buildings equipped with exhaust air heat pumps (EAHP) [J].
Fracastoro, Gian Vincenzo ;
Serraino, Matteo .
ENERGY AND BUILDINGS, 2010, 42 (08) :1283-1289
[7]   Study of a prototype of an advanced mechanical ventilation system with heat recovery integrated by heat pump [J].
Fucci, F. ;
Perone, C. ;
La Fianza, G. ;
Brunetti, L. ;
Giametta, F. ;
Catalano, P. .
ENERGY AND BUILDINGS, 2016, 133 :111-121
[8]   Energy performance comparison of three innovative HVAC systems for renovation through dynamic simulation [J].
Gustafsson, Marcus ;
Dermentzis, Georgios ;
Myhren, Jonn Are ;
Bales, Chris ;
Ochs, Fabian ;
Holmberg, Sture ;
Feist, Wolfgang .
ENERGY AND BUILDINGS, 2014, 82 :512-519
[9]   Performance improvement of air-cooled refrigeration system by using evaporatively cooled air condenser [J].
Hajidavalloo, E. ;
Eghtedari, H. .
INTERNATIONAL JOURNAL OF REFRIGERATION-REVUE INTERNATIONALE DU FROID, 2010, 33 (05) :982-988
[10]   Application of evaporative cooling on the condenser of window-air-conditioner [J].
Hajidavalloo, Ebrahim .
APPLIED THERMAL ENGINEERING, 2007, 27 (11-12) :1937-1943