Novel voltage-to-power sensitivity estimation for phasor measurement unit-unobservable distribution networks based on network equivalent

被引:13
作者
Su, Hongzhi [1 ]
Wang, Chengshan [1 ]
Li, Peng [1 ,2 ]
Li, Peng [1 ,2 ]
Liu, Zhelin [1 ]
Wu, Jianzhong [3 ]
机构
[1] Tianjin Univ, Key Lab Smart Grid, Minist Educ, Tianjin 300072, Peoples R China
[2] CSG, Power Res Inst, Guangzhou 510663, Guangdong, Peoples R China
[3] Cardiff Univ, Inst Energy, Sch Engn, Cardiff CF24 3AA, S Glam, Wales
关键词
phasor measurement unit (PMU); Distribution network; Model equivalent; Maximum correntropy Kalman filter (MCKF); Voltage-to-power sensitivity; ACTIVE DISTRIBUTION NETWORKS; SOFT OPEN POINTS; DISTRIBUTION-SYSTEMS; HIGH PENETRATION; STATE ESTIMATION; IDENTIFICATION; SYNCHROPHASORS; OPERATION; IMPACTS; FLOW;
D O I
10.1016/j.apenergy.2019.05.018
中图分类号
TE [石油、天然气工业]; TK [能源与动力工程];
学科分类号
0807 ; 0820 ;
摘要
The access and application of phasor measurement units (PMUs) in distribution networks highly improve the system observability and further enhance the performance of operation control and energy management. A novel PMU-based estimation method of voltage-to-power sensitivity via network equivalent is proposed for distribution systems. An equivalent model is introduced to simplify the PMU-unobservable parts of the distribution network. The equivalent parameters are estimated with the PMU measurements on both sides. The original PMU-unobservable distribution network is simplified into a completely observable network with an arbitrary configuration of PMUs. The maximum correntropy Kalman filter (MCKF) is exploited in parameter estimation to handle the noise and bad data within the PMU measurements. The voltage-to-power sensitivity of the simplified system is then calculated according to the estimation of the equivalent network parameters. Case studies on the IEEE 33-node and the PG&E 69-node test feeders verify the correctness and effectiveness of the proposed method.
引用
收藏
页码:302 / 312
页数:11
相关论文
共 55 条
[1]   Online Thevenin Equivalent Determination Considering System Side Changes and Measurement Errors [J].
Abdelkader, Sobhy M. ;
Morrow, D. John .
IEEE TRANSACTIONS ON POWER SYSTEMS, 2015, 30 (05) :2716-2725
[2]   State estimation of medium voltage distribution networks using smart meter measurements [J].
Al-Wakeel, Ali ;
Wu, Jianzhong ;
Jenkins, Nick .
APPLIED ENERGY, 2016, 184 :207-218
[3]   Peer-to-peer-based integrated grid voltage support function for smart photovoltaic inverters [J].
Almasalma, Hamada ;
Claeys, Sander ;
Deconinck, Geert .
APPLIED ENERGY, 2019, 239 :1037-1048
[4]  
Arghandeh Reza, 2015, 2015 IEEE Power & Energy Society General Meeting, P1, DOI 10.1109/PESGM.2015.7286053
[5]   Identification and Estimation of Erroneous Transmission Line Parameters Using PMU Measurements [J].
Asprou, Markos ;
Kyriakides, Elias .
IEEE TRANSACTIONS ON POWER DELIVERY, 2017, 32 (06) :2510-2519
[6]   OPTIMAL CAPACITOR PLACEMENT ON RADIAL-DISTRIBUTION SYSTEMS [J].
BARAN, ME ;
WU, FF .
IEEE TRANSACTIONS ON POWER DELIVERY, 1989, 4 (01) :725-734
[7]   NETWORK RECONFIGURATION IN DISTRIBUTION-SYSTEMS FOR LOSS REDUCTION AND LOAD BALANCING [J].
BARAN, ME ;
WU, FF .
IEEE TRANSACTIONS ON POWER DELIVERY, 1989, 4 (02) :1401-1407
[8]   Enhancing Observability in Distribution Grids Using Smart Meter Data [J].
Bhela, Siddharth ;
Kekatos, Vassilis ;
Veeramachaneni, Sriharsha .
IEEE TRANSACTIONS ON SMART GRID, 2018, 9 (06) :5953-5961
[9]   An Optimal Thevenin Equivalent Estimation Method and its Application to the Voltage Stability Analysis of a Wind Hub [J].
Burchett, Stephen M. ;
Douglas, Daniel ;
Ghiocel, Scott G. ;
Liehr, Maximilian W. A. ;
Chow, Joe H. ;
Kosterev, Dmitry ;
Faris, Anthony ;
Heredia, Eric ;
Matthews, Gordon H. .
IEEE TRANSACTIONS ON POWER SYSTEMS, 2018, 33 (04) :3644-3652
[10]   Maximum correntropy Kalman filter [J].
Chen, Badong ;
Liu, Xi ;
Zhao, Haiquan ;
Principe, Jose C. .
AUTOMATICA, 2017, 76 :70-77