System-level experimental investigations of the direct immersion cooling data center units with thermodynamic and thermoeconomic assessments

被引:77
作者
Kanbur, Baris Burak [1 ]
Wu, Chenlong [1 ,2 ]
Fan, Simiao [1 ,2 ]
Duan, Fei [1 ]
机构
[1] Nanyang Technol Univ, Sch Mech & Aerosp Engn, Singapore 639798, Singapore
[2] Nanyang Technol Univ, Energy Res Inst NTU, Singapore 637141, Singapore
关键词
Data center cooling; Thermodynamic analysis; Economic analysis; Thermal management; Immersion cooling; Life cycle costing; THERMAL MANAGEMENT; ECONOMIC-ANALYSIS; AIR;
D O I
10.1016/j.energy.2020.119373
中图分类号
O414.1 [热力学];
学科分类号
摘要
The study is to perform thermodynamic, economic and thermoeconomic assessments for two different direct immersion cooling data center systems which are the single-phase and the two-phase immersion cooling systems with the operating ranges of 3.2-27.6 kW and 6.8-15.9 kW, respectively. The two-phase cooling system achieves 72-79% better coefficient of performance trends than the single-phase cooling system. According to the present worth method, the replacement and the energy costs are found as the most dominant future cost terms for the two-phase and the single-phase cooling systems, respectively. The annual exergy cost of the two-phase cooling system is found up to 4.91 times the annual energy costs due to the dominant effects of the destruction and loss terms. Moreover, both cooling data center systems are compared to the existing air-cooled data center unit. They are found economically infeasible for the server power rates below 5 kW because of their higher capital investment costs while they become more affordable for higher server power rates with lower future cost terms. (C) 2020 Elsevier Ltd. All rights reserved.
引用
收藏
页数:14
相关论文
共 33 条
  • [11] Thermal Management Challenges in Telecommunication Systems and Data Centers
    Garimella, Suresh V.
    Yeh, Lian-Tuu
    Persoons, Tim
    [J]. IEEE TRANSACTIONS ON COMPONENTS PACKAGING AND MANUFACTURING TECHNOLOGY, 2012, 2 (08): : 1307 - 1316
  • [12] Combined heat and power generation via hybrid data center cooling-polymer electrolyte membrane fuel cell system
    Kanbur, Baris B.
    Wu, Chenlong
    Duan, Fei
    [J]. INTERNATIONAL JOURNAL OF ENERGY RESEARCH, 2020, 44 (06) : 4759 - 4772
  • [13] Two-phase liquid-immersion data center cooling system: Experimental performance and thermoeconomic analysis
    Kanbur, Baris Burak
    Wu, Chenlong
    Fan, Simiao
    Tong, Wei
    Duan, Fei
    [J]. INTERNATIONAL JOURNAL OF REFRIGERATION, 2020, 118 : 290 - 301
  • [14] Multi-criteria thermoeconomic and thermodynamic assessments of the desalination-integrated two-phase liquid-immersion data center cooling system
    Kanbur, Baris Burak
    Wu, Chenlong
    Duan, Fei
    [J]. INTERNATIONAL JOURNAL OF ENERGY RESEARCH, 2020, 44 (13) : 10453 - 10470
  • [15] Thermoeconomic assessment of a micro cogeneration system with LNG cold utilization
    Kanbur, Baris Burak
    Xiang, Liming
    Dubey, Swapnil
    Choo, Fook Hoong
    Duan, Fei
    [J]. ENERGY, 2017, 129 : 171 - 184
  • [16] A Review on efficient thermal management of air- and liquid-cooled data centers: From chip to the cooling system
    Khalaj, Ali Habibi
    Halgamuge, Saman K.
    [J]. APPLIED ENERGY, 2017, 205 : 1165 - 1188
  • [17] Impact of integrated hot water cooling and desiccant-assisted evaporative cooling systems on energy savings in a data center
    Kim, Min-Hwi
    Ham, Sang-Woo
    Park, Jun-Seok
    Jeong, Jae-Weon
    [J]. ENERGY, 2014, 78 : 384 - 396
  • [18] Influence of cooling architecture on data center power consumption
    Moazamigoodarzi, Hosein
    Tsai, Peiying Jennifer
    Pal, Souvik
    Ghosh, Suvojit
    Puri, Ishwar K.
    [J]. ENERGY, 2019, 183 : 525 - 535
  • [19] DESCRIBING THE UNCERTAINTIES IN EXPERIMENTAL RESULTS
    MOFFAT, RJ
    [J]. EXPERIMENTAL THERMAL AND FLUID SCIENCE, 1988, 1 (01) : 3 - 17
  • [20] National Institute of Standards and Technology, THERMOPHYSICAL PROPE