System-level experimental investigations of the direct immersion cooling data center units with thermodynamic and thermoeconomic assessments

被引:77
作者
Kanbur, Baris Burak [1 ]
Wu, Chenlong [1 ,2 ]
Fan, Simiao [1 ,2 ]
Duan, Fei [1 ]
机构
[1] Nanyang Technol Univ, Sch Mech & Aerosp Engn, Singapore 639798, Singapore
[2] Nanyang Technol Univ, Energy Res Inst NTU, Singapore 637141, Singapore
关键词
Data center cooling; Thermodynamic analysis; Economic analysis; Thermal management; Immersion cooling; Life cycle costing; THERMAL MANAGEMENT; ECONOMIC-ANALYSIS; AIR;
D O I
10.1016/j.energy.2020.119373
中图分类号
O414.1 [热力学];
学科分类号
摘要
The study is to perform thermodynamic, economic and thermoeconomic assessments for two different direct immersion cooling data center systems which are the single-phase and the two-phase immersion cooling systems with the operating ranges of 3.2-27.6 kW and 6.8-15.9 kW, respectively. The two-phase cooling system achieves 72-79% better coefficient of performance trends than the single-phase cooling system. According to the present worth method, the replacement and the energy costs are found as the most dominant future cost terms for the two-phase and the single-phase cooling systems, respectively. The annual exergy cost of the two-phase cooling system is found up to 4.91 times the annual energy costs due to the dominant effects of the destruction and loss terms. Moreover, both cooling data center systems are compared to the existing air-cooled data center unit. They are found economically infeasible for the server power rates below 5 kW because of their higher capital investment costs while they become more affordable for higher server power rates with lower future cost terms. (C) 2020 Elsevier Ltd. All rights reserved.
引用
收藏
页数:14
相关论文
共 33 条
  • [1] [Anonymous], 2015, PAR AGR
  • [2] Bejan A., 1996, Thermal design and optimization
  • [3] Experimental investigation of microchannel coolers for the high heat flux thermal management of GaN-on-SiC semiconductor devices
    Calame, J. P.
    Myers, R. E.
    Binarl, S. C.
    Wood, F. N.
    Garven, M.
    [J]. INTERNATIONAL JOURNAL OF HEAT AND MASS TRANSFER, 2007, 50 (23-24) : 4767 - 4779
  • [4] Energy saving evaluation of a novel energy system based on spray cooling for supercomputer center
    Chen, Hua
    Cheng, Wen-long
    Zhang, Wei-wei
    Peng, Yu-hang
    Jiang, Li-jia
    [J]. ENERGY, 2017, 141 : 304 - 315
  • [5] An experimental study of two-phase multiple jet cooling on finned surfaces using a dielectric fluid
    Chien, Liang-Han
    Chang, Chin-Yao
    [J]. APPLIED THERMAL ENGINEERING, 2011, 31 (11-12) : 1983 - 1993
  • [6] Economic analysis of data center cooling strategies
    Cho, Kyuman
    Chang, Hyunjae
    Jung, Yongho
    Yoon, Yoojung
    [J]. SUSTAINABLE CITIES AND SOCIETY, 2017, 31 : 234 - 243
  • [7] Potentiometric and economic analysis of using air and water-side economizers for data center cooling based on various weather conditions
    Deymi-Dashtebayaz, Mahdi
    Namanlo, Sajad Valipour
    [J]. INTERNATIONAL JOURNAL OF REFRIGERATION, 2019, 99 : 213 - 225
  • [8] Energy Market Authority, 2019, SING EN STAT 2018
  • [9] Energy Market Authority, 2019, EL TAR
  • [10] Advances in data center thermal management
    Fulpagare, Yogesh
    Bhargav, Atul
    [J]. RENEWABLE & SUSTAINABLE ENERGY REVIEWS, 2015, 43 : 981 - 996