Estimation of explosion overpressure associated with background leakage in natural gas pipelines

被引:15
作者
Liu, Cuiwei [1 ,3 ]
Liao, Yihan [1 ]
Yang, Wen [2 ]
Yin, Yuanbo [1 ,3 ]
Wang, Yazhen [1 ]
Cui, Gan [1 ]
Li, Yuxing [1 ]
机构
[1] China Univ Petr Huadong, Qingdao 266580, Peoples R China
[2] PipeChina South China Co, Guangzhou 510620, Peoples R China
[3] Shenzhen Engn Res Ctr Gas Distribut & Efficient U, Shenzhen, Peoples R China
基金
中国国家自然科学基金;
关键词
Natural gas pipelines; Gas cloud explosion; Volume; Building; Overpressure; VAPOR CLOUD EXPLOSIONS; BLAST WAVE; VENTED GAS; RISK-ASSESSMENT; PRESSURE PREDICTION; FLAME PROPAGATION; HYDROGEN; SIMULATION; METHANE; DEFLAGRATION;
D O I
10.1016/j.jngse.2021.103883
中图分类号
TE [石油、天然气工业]; TK [能源与动力工程];
学科分类号
0807 ; 0820 ;
摘要
Gathered natural gas (NG) clouds caused by background leakage from buried municipal gas pipelines or those used by gas stations pose potential threats to humans and the environment. If the leaked gas cloud (GC) ignited, significant injury caused by the explosion could occur. Therefore, the influences of the outside overpressure on the outside and inside of the building should be predicted to evaluate the damage level. Moreover, when the generated explosion overpressure is calculated, it is generally assumed that the entire GC is ignited, and its shape is hemispheric, which need further study and confirmation for background leakages. In this work, the actual explosion volume of a cubic leaked NG cloud is determined by establishing a generation model for the overpressure peak value with the help of numerical simulations and experiments, and the overpressure distribution outside and inside the building is evaluated by establishing a propagation model, using numerical simulations. The results show that for a cubic NG cloud, the actual explosion volume is 0.07 times the total volume of the leaked GC, by which the peak generation can be accurately predicted with errors smaller than 15%. Considering the influences of the building on the peak, the positive and negative peak outside and inside of the building can also be evaluated with small errors, which helps to identify safe places for people facing a VCE explosion.
引用
收藏
页数:17
相关论文
共 67 条
  • [1] Investigation of the Explosion Behaviour Affected by the Changes of Particle Size
    Ab Kadir, Noor Ain
    Rusli, Risza
    Buang, Azizul
    Rahim, Nur Shamimi Abdul
    [J]. PROCEEDING OF 4TH INTERNATIONAL CONFERENCE ON PROCESS ENGINEERING AND ADVANCED MATERIALS (ICPEAM 2016), 2016, 148 : 1156 - 1161
  • [2] [Anonymous], 1973, EXPLOSION DYNAMICS I
  • [3] [Anonymous], 2009, 12 0 US GUID US INP
  • [4] Management of primary blast injury
    Argyros, GJ
    [J]. TOXICOLOGY, 1997, 121 (01) : 105 - 115
  • [5] Arntzen B.J, 1998, MODELLING TURBULENCE
  • [6] Baker W., 1983, FUNDAMENTAL STUDIES
  • [7] Characterising the distribution of methane and carbon dioxide emissions from the natural gas supply chain
    Balcombe, P.
    Brandon, N. P.
    Hawkes, A. D.
    [J]. JOURNAL OF CLEANER PRODUCTION, 2018, 172 : 2019 - 2032
  • [8] Experimental investigation on the deflagration load under unconfined methane-air explosions
    Bao, Qi
    Fang, Qin
    Yang, Shigang
    Zhang, Yadong
    Xiang, Hengbo
    Chen, Li
    Li, Zhan
    [J]. FUEL, 2016, 185 : 565 - 576
  • [9] Bi M, 2001, RES PRESSURE FIELDS
  • [10] Comparison between FLACS explosion simulations and experiments conducted in a PWR Steam Generator casemate scale down with hydrogen gradients
    Bleyer, A.
    Taveau, J.
    Djebaili-Chaumeix, N.
    Paillard, C. E.
    Bentaib, A.
    [J]. NUCLEAR ENGINEERING AND DESIGN, 2012, 245 : 189 - 196