Thermal response and failure mode evaluation of a dry-type transformer

被引:30
作者
Blanco Alonso, Pelayo E. [1 ]
Meana-Fernandez, Andres [1 ]
Fernandez Oro, Jesus M. [1 ]
机构
[1] Univ Oviedo, Dept Energy, Fluid Mech Area, C Wifredo Ricart S-N, Gijon 33203, Asturias, Spain
关键词
Numerical analysis; Electrothermal effects; Power transformer losses; Power transformer insulation; Failure analysis; HOT-SPOT TEMPERATURE; POWER TRANSFORMER; HEAT-TRANSFER; CORE JOINTS; FLUID-FLOW;
D O I
10.1016/j.applthermaleng.2017.04.007
中图分类号
O414.1 [热力学];
学科分类号
摘要
In this work, the safe working limits of a 10 kVA dry-type transformer with H-class insulation are determined by modeling its thermal response in different scenarios using numerical simulations (CFD). A numerical model of the heat transfer from the transformer to its surroundings by natural convection has been developed. Firstly, a steady regime with the transformer working at full load at an ambient temperature of 300 K is studied in order to gain insight into the heat transmission mechanisms. Then, a series of 32 steady simulations with different load and ambient conditions is performed to characterize insulation aging due to overheating. Finally, a second group of 9 transient simulations is employed to assess the transformer failure time under an overload situation. The results show a coupling between the thermal and flow fields. The hot spot temperatures obtained by the model are consistent with previous experimental observations and the time that the transformer resists an overload has been calculated. The results obtained allow the prediction of the thermal behavior of a transformer under different scenarios, reducing the need for instrumentation, as well as experimental tests which result in the loss of the testing transformer. (C) 2017 Elsevier Ltd. All rights reserved.
引用
收藏
页码:763 / 771
页数:9
相关论文
共 23 条
[1]  
[Anonymous], 2004, TRANSFORMER INDUCTOR
[2]  
[Anonymous], 2007, IEEE POW ENG SOC GEN
[3]   The Influence of Modeling Transformer Age Related Failures on System Reliability [J].
Awadallah, Selma K. E. ;
Milanovic, Jovica V. ;
Jarman, Paul N. .
IEEE TRANSACTIONS ON POWER SYSTEMS, 2015, 30 (02) :970-979
[4]  
Bejan A., 2013, Convective heat transfer
[5]   Numerical study of heat transfer and fluid flow in a power transformer [J].
El Wakil, N ;
Chereches, NC ;
Padet, J .
INTERNATIONAL JOURNAL OF THERMAL SCIENCES, 2006, 45 (06) :615-626
[6]  
Ferziger J.H., 2001, Computational Methods for Fluid Dynamics
[7]  
Ghareh M., 2008, WORLD ACAD SCI ENG T, V2, P290
[8]  
Ghiaasiaan S.M., 2011, Convective Heat and Mass Transfer
[9]  
IEEE, 1989, TECHNICAL REPORT
[10]  
Kundu P. K., 2015, Fluid Mechanics, DOI DOI 10.1016/C2012-0-00611-4